Table of Contents Table of Contents
Previous Page  17 / 73 Next Page
Information
Show Menu
Previous Page 17 / 73 Next Page
Page Background

16

Supply characteristics,

a

100...240 V products

Type

SR2

ppp

1FU

SR2 

p

121FU

SR2 

p

201FU

SR3 B101FU SR3 B261FU

Nominal voltage

V

a

100…240

Voltage limits

V

a

85…264

Nominal frequency

Hz

50-60

Nominal input current

Without extensions

mA

80/30

100/50

80/30

100/50

With extensions

mA

80/40

80/60

Power dissipated

Without extensions

VA

7

11

7

12

With extensions

VA

12

17

Micro-breaks

Permissible duration

ms

10

rms insulation voltage

V

a

1780

Discrete input characteristics,

a

100...240 V products

Type

SR

p pppp

FU

Nominal value of inputs

Voltage

V

a

100... 240

Current

mA

0.6

Frequencies

Hz

47...53 and 57...63

Input switching limit values

At state 1

Voltage

V

u a

79

Current

mA

> 0.17

At state 0

Voltage

V

y a

40

Current

mA

< 0.5

Input impedance at state 1

K

350

Response

time

LADDER

language

State 0 to 1 (50/60 Hz)

ms

50

State 1 to 0 (50/60 Hz)

ms

50

FBD

language

State 0 to 1 (50/60 Hz)

ms

50 min., 255 max. (in increments of 10)

State 1 to 0 (50/60 Hz)

ms

50 min., 255 max. (in increments of 10)

Isolation

Between supply and inputs

None

Between inputs

None

Protection

Against inversion of terminals

Yes (control instructions not executed)

Relay output characteristics,

a

100...240 V products

Type

SR2 

p

101FU

SR2 

p

121FU

SR3 B101FU

SR3 XT101FU

SR2 

p

201FU SR3 B261FU SR3 XT61FU SR3 XT141FU

Operating limit values

V

c

5...30,

a

24...250

Contact type

N/O

Thermal current

A

4 outputs: 8 A 8 outputs: 8 A 8 outputs: 8 A

2 outputs: 5 A

2 outputs: 8 A 4 outputs: 8 A

2 outputs: 5 A

Electrical durability for

500 000 operating cycles

Conforming to

IEC/EN 60947-5-1

Utilisation

category

DC-12

V

c

24

A

1.5

DC-13

V

c

24 (L/R = 10 ms)

A

0.6

AC-12

V

a

230

A

1.5

AC-15

V

a

230

A

0.9

Minimum switching

capacity

At minimum voltage

of

c

12 V

mA

10

Low power switching

reliability of contact

c

12 V - 10 mA

Maximum operating rate

No-load

Hz

10

At Ie (operational current)

Hz

0.1

Mechanical life

In millions of operating cycles

10

Rated impulse

withstand voltage

Conforming to IEC/EN 60947-1

and IEC/EN 60664-1

kV

4

Response time

Set

ms

10

Reset

ms

5

Built-in protection

Against short-circuits

None

Against overvoltage

and overload

None

Presentation :

pages 6 to 9

Functions :

pages 10 to 12

Curves :

pages 20 and 21

References :

pages 22 to 27

Dimensions, schemes :

pages 28 to 31

Characteristics

(continued)

1

Zelio Logic smart relays

1

Compact and modular smart relays

1

2

3

4

5

6

7

8

9

10