20
Electrical durability of relay outputs
(in millions of operating cycles, conforming to IEC/EN 60947-5-1)
d.c. loads
DC-12
(1)
DC-13
(2)
(1) DC-12: control of resistive loads and of solid state loads isolated by opto-coupler, L/R
y
1 ms.
(2) DC-13: switching electromagnets, L/R
y
2 x (Ue x Ie) in ms, Ue: rated operational voltage,
Ie: rated operational current (with a protection diode on the load, DC-12 curves must be used
with a coefficient of 0.9 applied to the number in millions of operating cycles).
0
1,5
1
2
0,5
0,0
0,5
1,0
1,5
2,0
2,5
3,0
24 V
Millions of operating cycles
Current (A)
0,1
0,3
0,5
0,7
0,9 1
0,2
0,4
0,6
0,8
0,0
1,4
1,2
1,0
0,8
0,6
0,4
0,2
L/R = 10 ms 24 V
L/R = 60 ms 24 V
Millions of operating cycles
Current (A)
Presentation :
pages 6 to 9
Functions :
pages 10 to 12
Characteristics :
pages 14 to 19
References :
pages 22 to 27
Dimensions, schemes :
pages 28 to 31
Curves
1
Zelio Logic smart relays
1
Compact and modular smart relays
1
2
3
4
5
6
7
8
9
10