D-65

Designing customer

connections

Withdrawable Compact NS630b to

NS1600, rear connection

Customer connection

Flat bars, 10 mm thick

Devices

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NS630b Size per

phase

1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

630

630

630

630

630

630

630

630

630

630

630

NS800 Size per

phase

1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

800

800

800

800

800

800

800

800

800

800

800

NS1000 Size per

phase

1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

1000

1000

1000

1000

1000

1000

1000

1000

1000

960

1000

NS1250 Size per

phase

1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10

b

I (A)

1250

1250

1250

1250

1250

1210

1250

1160

1210

1110

1160

NS1600 Size per

phase

1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10

b

I (A)

1560

1430

1520

1430

1480

1380

1430

1330

1380

1280

1330

b

connection not possible.

Canalis connection

For Canalis connections, apply the appropriate derating coefficient K.

AppareilDevices

NS630b NS800 NS1000 NS1250 NS1600

Derating

coefficient K

1

1

1

1

0.98

Note:

the values indicated above have been validated for Prisma Plus switchboards.

Additional informations

Designing electrical