Table of Contents Table of Contents
Previous Page  311 / 356 Next Page
Information
Show Menu
Previous Page 311 / 356 Next Page
Page Background

Customer connection

Flat bars, 10 mm thick

Devices

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NS630b Size per

phase

1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

630

630

630

630

630

630

630

630

630

630

630

NS800 Size per

phase

1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

800

800

800

800

800

800

800

800

800

800

800

NS1000 Size per

phase

1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

1000

1000

1000

1000 1000

1000

1000

1000

1000

970

1000

NS1250 Size per

phase

1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10

b

I (A)

1250

1250

1250 1250

1250

1250

1250

1180

1230

1130

1180

NS1600 Size per

phase

1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10

b

I (A)

1600

1550

1600

1500 1550

1450

1500

1400

1450

1350

1400

b

connection not possible.

Canalis connection

For Canalis connections, apply the appropriate derating coefficient K.

Devices

NS630b NS800 NS1000 NS1250 NS1600

Derating

coefficient K

1

1

1

1

0.98

Note:

the values indicated above have been validated for Prisma Plus switchboards.

Designing customer

connections

Fixed Compact NS630b to NS1600

Rear connection

D-63

Additional informations

Designing electrical

characteristics