Table of Contents Table of Contents
Previous Page  308 / 356 Next Page
Information
Show Menu
Previous Page 308 / 356 Next Page
Page Background

D-60

Customer connection

Flat bars, 10 mm thick

Devices

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NT06 Size per

phase

1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

630

630

630

630

630

630

630

630

630

630

630

NT08 Size per

phase

1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

800

800

800

800

800

800

800

800

800

800

800

NT10 Size per

phase

1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

1000

1000

1000

1000 1000

1000

1000

1000

1000

960

1000

NT12 Size per

phase

1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10

b

I (A)

1250

1250

1250

1250 1250

1210

1250

1160

1210

1110

1160

NT16 Size per

phase

1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10

b

I (A)

1560

1430

1520

1430 1480

1380

1430

1330

1380

1280

1330

b

connection not possible.

Canalis connection

For Canalis connections, apply the appropriate derating coefficient K.

Devices

NT06 NT08 NT10 NT12 NT16

Derating

coefficient K

1

1

1

1

0.98

Note:

the values indicated above have been validated for Prisma Plus switchboards.

Designing customer

connections

Drawout Masterpact NT06 to NT16

Rear connection

Additional informations

Designing electrical

characteristics