D-58
Customer connection
Flat bars, 10 mm thick
Devices
Permissible current (A)
Ambient temperature around the switchboard
25 °C
30 °C
35 °C
40 °C
45 °C
50 °C
IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31 IP
y
31 IP > 31
NT06 Size per
phase
1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10
b
I (A)
630
630
630
630
630
630
630
630
630
630
630
NT08 Size per
phase
1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10
b
I (A)
800
800
800
800
800
800
800
800
800
800
800
NT10 Size per
phase
1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10
b
I (A)
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
NT12 Size per
phase
1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10
b
I (A)
1250
1250
1250
1250
1250
1250
1250
1250
1250
1180
1230
NT16 Size per
phase
1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10
b
I (A)
1600
1570
1600
1520
1570
1470
1520
1420
1470
1370
1420
b
connection not possible.
Canalis connection
For Canalis connections, apply the appropriate derating coefficient K.
Devices
NT06b NT08 NT10 NT12 NT16
Derating
coefficient K
1
1
1
1
0.98
Note:
the values indicated above have been validated for Prisma Plus switchboards.
Designing customer
connections
Fixed Masterpact NT06 to NT16
Rear connection
Additional informations
Designing electrical
characteristics