Table of Contents Table of Contents
Previous Page  306 / 356 Next Page
Information
Show Menu
Previous Page 306 / 356 Next Page
Page Background

D-58

Customer connection

Flat bars, 10 mm thick

Devices

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NT06 Size per

phase

1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

630

630

630

630

630

630

630

630

630

630

630

NT08 Size per

phase

1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

800

800

800

800

800

800

800

800

800

800

800

NT10 Size per

phase

1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

NT12 Size per

phase

1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10 1b 80x10

b

I (A)

1250

1250

1250

1250

1250

1250

1250

1250

1250

1180

1230

NT16 Size per

phase

1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10 1b100x10

b

I (A)

1600

1570

1600

1520

1570

1470

1520

1420

1470

1370

1420

b

connection not possible.

Canalis connection

For Canalis connections, apply the appropriate derating coefficient K.

Devices

NT06b NT08 NT10 NT12 NT16

Derating

coefficient K

1

1

1

1

0.98

Note:

the values indicated above have been validated for Prisma Plus switchboards.

Designing customer

connections

Fixed Masterpact NT06 to NT16

Rear connection

Additional informations

Designing electrical

characteristics