D-71
Type of premises
Enclosure or cubicle
Wall-mounted
enclosure
without door
with door
with door + canopy with door + canopy
+ gasket
IP55
Floor-standing
enclosure
without door
with door
with door + canopy with door + canopy
+ gasket
Cubicle
with fixed frame with door + IP30
cover
with door + gasket
+ IP30 cover
with door + IP55
cover
Min. IP/IK
required
IP30/IK07
IP30/IK08
IP31/IK08
IP43/IK08
IP55/IK10
IP IK
Buildings open to the general public
Shared premises of
buildings open to the
general public
storage rooms
20
08
b
packing rooms
20
08
b
archive rooms
20
02
b
film and magnetic
media storage
20
02
b
linen rooms
20
02
b
laundry rooms
24
07
b
misc. shops
21
07/08
b
kitchens (large)
J Reception old and handicapped
people
20
02
b
L Lecture halls,
meeting rooms,
auditoriums,
halls used for
several purposes
halls
20
02/07
b
stage areas
20
08
b
scenery storage
rooms
20
08
b
costume rooms
20
07
b
M Retail premises,
shopping malls
sales premises
20
08
b
areas for storage
and handling of
packing
20
08
b
N Restaurants and cafes
20
08
b
O Hotels and boarding houses
20
02
b
P Dance halls and gaming parlours
20
07
b
R Teaching
establishments,
holiday camps
classrooms
20
02
b
dormitories
20
08
b
S Libraries and documentation centres
20
02
b
T Exhibitions
halls and rooms
20
02
b
areas for recep ion
of equipment
and merchandise
20
07
b
U Healthcare
establishments
bedrooms
20
02
b
incineration
21
07/08
b
operating rooms
20
07
b
centralised
sterilisation
24
02/07
b
pharmacies and labs
with more than 10 l of
inflammable liquids
21
v
/23
b
02
v
/07
b
v
b
V Places of worship
20
02
b
W Administrative premises, banks
20
02
b
X Indoor sports
facilities
halls
20
07
v
/08
b
v
b
premises containing
refrigeration facilities
21
08
b
Y Museums
20
02
b
PA Covered open air facilities
23
v
/25
b
08
v
/10
b
v
b
CTS Marquees and tents
44
08
b
SG Inflatable structures
44
08
b
PS Covered parking lots
21
08
v
/10
b
v
b
Selection of enclosures
according to the premises
Additional informations
Enclosure characteristics