D-73

Type of premises

Enclosure or cubicle

Wall-mounted

enclosure

without door

with door

wi h door + canopy with door + canopy

+ gasket

IP55

Floor-standing

enclosure

without door

with door

wi h door + canopy with door + canopy

+ gasket

Cubicle

with fixed frame with door + IP30

cover

wi h door + gasket

+ IP30 cover

with door + IP55

cover

Min. IP/IK

required

IP30/IK07

IP30/IK08

IP31/IK08

IP43/IK08

IP55/IK10

IP IK

Farm premises or locations

Alcohol (storage)

23

07

b

Closed cattle sheds

35

07

b

Laundries

24

07

b

Wood storage rooms

30

10

b

Threshing floors

50

07

b

Distilling cellars

23

07

b

Vat rooms (wine)

23

07

b

Courtyards

35

07

b

Poultry barns

35

07

b

Stables

35

07

b

Fertiliser (storage)

50

07

b

Stables

35

07

b

Manure heaps

24

07

b

Haylofts

50

07

b

Haystacks, forage (storage)

50

07

b

Granaries, barns

50

07

b

Straw (storage)

50

07

b

Greenhouses

23

07

b

Grain silos

50

07

b

Milking rooms

35

07

b

Pig sties

35

07

b

Chicken houses

35

07

b

Miscellaneous installations

Fair facilities

33

08

b

Water treatment facilities

24/25 07/08

b

Thermodynamic installations, air-conditioned rooms and cold rooms

Height

above

ground

from 0 to 1.10 m 25

07

b

from 1.10 to 2 m 24

07

b

above 2 m under

evaporator or water

drain pipe

21

07

b

ceiling and up to 10

cm underneath

23

07

b

Temperature

y

-10 °C

23

07

b

Compressor room

21

08

b

integral unit located

outside or on a terrace

34

08

Selection of enclosures

according to the premises

Additional informations

Enclosure characteristics