D-73
Type of premises
Enclosure or cubicle
Wall-mounted
enclosure
without door
with door
wi h door + canopy with door + canopy
+ gasket
IP55
Floor-standing
enclosure
without door
with door
wi h door + canopy with door + canopy
+ gasket
Cubicle
with fixed frame with door + IP30
cover
wi h door + gasket
+ IP30 cover
with door + IP55
cover
Min. IP/IK
required
IP30/IK07
IP30/IK08
IP31/IK08
IP43/IK08
IP55/IK10
IP IK
Farm premises or locations
Alcohol (storage)
23
07
b
Closed cattle sheds
35
07
b
Laundries
24
07
b
Wood storage rooms
30
10
b
Threshing floors
50
07
b
Distilling cellars
23
07
b
Vat rooms (wine)
23
07
b
Courtyards
35
07
b
Poultry barns
35
07
b
Stables
35
07
b
Fertiliser (storage)
50
07
b
Stables
35
07
b
Manure heaps
24
07
b
Haylofts
50
07
b
Haystacks, forage (storage)
50
07
b
Granaries, barns
50
07
b
Straw (storage)
50
07
b
Greenhouses
23
07
b
Grain silos
50
07
b
Milking rooms
35
07
b
Pig sties
35
07
b
Chicken houses
35
07
b
Miscellaneous installations
Fair facilities
33
08
b
Water treatment facilities
24/25 07/08
b
Thermodynamic installations, air-conditioned rooms and cold rooms
Height
above
ground
from 0 to 1.10 m 25
07
b
from 1.10 to 2 m 24
07
b
above 2 m under
evaporator or water
drain pipe
21
07
b
ceiling and up to 10
cm underneath
23
07
b
Temperature
y
-10 °C
23
07
b
Compressor room
21
08
b
integral unit located
outside or on a terrace
34
08
Selection of enclosures
according to the premises
Additional informations
Enclosure characteristics