Table of Contents Table of Contents
Previous Page  290 / 356 Next Page
Information
Show Menu
Previous Page 290 / 356 Next Page
Page Background

D-42

Connection

Flat bars, 10 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NS630b Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

630

630

630

630

630

630

630

630

630

630

630

NS800 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

800

800

800

800

800

800

800

800

800

800

800

NS1000 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

1000

1000

1000

1000

1000

1000

1000

1000

1000

960

1000

NS1250 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

1250

1250

1250

1250

1250

1210

1250

1160

1210

1110

1160

NS1600

(1)

Size per phase 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10 2b 50 x 10

b

I (A)

1560

1430

1520

1430

1480

1380

1430

1330

1380

1280

1330

(1) Make the neutral connection with one bar, 50 x 10 mm.

Horizontal link

Flat bars, 10 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NS630b Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

630

630

630

630

630

630

630

630

630

630

630

NS800 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

800

800

800

800

800

800

800

800

800

800

800

NS1000 Size per phase 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10 1b 50 x 10

b

I (A)

1000

1000

1000

1000

1000

1000

1000

1000

1000

970

1000

NS1250 Size per phase 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10 1b 60 x 10

b

I (A)

1250

1250

1250

1250

1250

1210

1250

1160

1210

1110

1160

NS1600 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10

b

I (A)

1560

1430

1520

1430

1480

1380

1430

1330

1380

1280

1330

b

connection not possible.

Note:

the values indicated above have been validated for Prisma Plus switchboards.

Designing connections

u

630 A

between a device and busbars

Compact circuit breakers

Withdrawable NS630b to NS1600

Additional informations

Designing electrical

characteristics