LinergyBW
Insulatedbusbars up to630A
Linergydistributionsystems
Power busbars
Linergy BW busbar
125 A
160 A
250 A
400 A
630 A
Rated peak withstand current
(Ipk)
20 kÂ
30 kÂ
30 kÂ
52.5 kÂ
52.5 kÂ
Rated insulation voltage
(Ui)
500 V AC
750 V AC
750 V AC
750 V AC
1000 V AC
Rated impulse withstand voltage
(Uimp) 8 kV
8 kV
8 kV
8 kV
8 kV
Rated short-time current
(Icw)
8.5 kA rms / 1 s 10 kA rms / 1 s
13 kA rms / 1 s
20 kA rms / 1 s
25 kA rms / 1 s
Thermal stress
(A².s)
7.225 x 10
7
1.000 x 10
8
1.690 x 10
8
4.000 x 10
8
6.250 x 10
8
Length (mm)
450
750
1000 1400 1000 1400 1000 1400 1000 1400
Catalogue numbers
3P 04103 04107 04111 04116 04112 04117 04113 04118 04114 04119
4P 04104 04108 04121 04126 04122 04127 04123 04128 04124 04129
Spare parts
DD384952_L13-LIN.eps
Linergy BW busbar supports
Rated operational current at 40 °C
(Ie) 125 A
160 A
250 A
400 A
630 A
Composition
2 busbar supports + 2 end caps + packet of fixing accessories
Catalogue numbers
-
01210
01210
01210
01211
DD384951_L13-LIN.eps
IPxxB clip-on covers
Length (mm)
200
Set of
2
Catalogue numbers
-
01201
01201
01201
01201
Accessories
DD383498-LIN.eps
DD383472-LIN.eps
DD381385-LIN.eps
PB502375.eps
IPxxB tap-off terminals
200 A
connections
IPxxB insulating covers
Class 8.8 fixing
accessories
12 tap-off blocks
For 1 cable of 6 mm
2
(32 Amax.)
and 1 cable of 10 mm
2
(40 Amax.)
Ui: 750 V
In: 55 Amax.
(1)
12 tap-off blocks
For 1 cable of 1 to 16 mm
2
Ui: 750 V
In: 55 Amax. with only
1 cable
Covers which can be clipped on
and cut to size are used to
isolate the connectors of a
connection with cables of
cross-section 10 to 25 mm
2
M6 x 12 + 20 M6 contact
washers
Used for connecting b
b
All switchgear
equipped with enclosed
terminals
b
b
Linergy FM 160/200 A
b
b
All switchgear equipped
with enclosed terminals
b
b
Linergy FM
63/80/160/200 A
b
b
Linergy FM
200 A
Set of
12
12
4
8
20
Catalogue numbers 04151
04152
04021
04150
04158
(1)
Imax = 55 A for all connected cables.
PD390337.eps
Description
b
b
Compact busbar,
IPxxB
, ready for installation (supplied complete with supports
and end caps)
b
b
Shaped busbar, threaded M6 with 25-mm pitch, can be cut with 200-mm pitch
(150 mm for the 125 A)
b
b
Busbar installed on insulating supports, screwed onto the rear uprights
b
b
Wide selection of tested pre-wired connectors
b
b
Clip-on covers to protect against direct contact (IPxxB). Can easily be cut to allow
connections to pass through to the switchgear
b
b
Ends protected by end caps
84