PB104499-7.eps
PB500924.eps
IEC 60947-7-1, IEC 61439-2
Description
b
b
Downstream circuits are connected from the front, to spring terminals.
b
b
Contact pressure automatically adapts to the size of the conductor.
b
b
Contacts are insensitive to vibrations and thermal variations.
b
b
Only one cable (flexible or rigid) can be inserted per terminal.
Linergydistributionsystems
Distribution blocks
LinergyDX
Quick distributionblocks
Quick distribution blocks
Number of poles
4P, upstream incoming
4P, downstream incoming
PB104500-6.eps
PB104499-6.eps
Rated operational current at 40 °C
(Ie)
63 A
63 A
Rated conditional short-circuit breaker
of an assembly
(Isc)
The reinforced breaking capacity due to cascading in
circuit breaker combinations is maintained.
The worst-case situations have been tested.
The reinforced breaking capacity due to cascading
in circuit breaker combinations is maintained.
The worst-case situations have been tested.
Rated peak withstand current
(Ipk)
-
-
Rated insulation voltage
(Ui)
500 V AC
500 V AC
Rated operational voltage
(Ue)
440 V AC
440 V AC
Rated impulse withstand voltage
(Uimp)
6 kV
6 kV
Rated short-time current Icw
(Icw)
Thermal stress
(A².s)
-
-
Rated operational frequency
50/60 Hz
50/60 Hz
Degree of protection
IPxxB
IPxxB
Incoming terminals
1 tunnel terminal 25²/Ph
1 tunnel terminal 25²/Ph
Total connection capacity, outgoing terminals
24 connections:
4 x 6²/phase
12 x 6²/neutral
24 connections:
4 x 6²/phase
12 x 6²/neutral
Dimensions (H x W x D)
96.5 x 72 x 62
8 x 9 mm pitch
96.5 x 72 x 62
8 x 9 mm pitch
Installation
Clipped onto a DIN rail
Clipped onto a DIN rail
Other
Standard for installation inside Prisma
IEC 61439-2
IEC 61439-2
Glow-wire 60695-2-11
960 °C
960 °C
Degree of pollution
3
3
Catalogue numbers
04040
04041
Accessories
Catalogue numbers
-
-
90