Installation
Dd381346-70-LGI.eps
Directly on the mounting plates of horizontally mounted
Compact
NSX100/250
and Compact
INS250
devices in the
enclosures.
DD380780-70-LGI.eps
It can also be mounted downstream of vertically mounted
Compact
NSX100/250
and Compact
INS250
devices in the
enclosures.
In this case, the Linergy DP is mounted on a depth-adjustable
modular rail.
Technical data
Common characteristics
Rated conditional short-circuit
current of an assembly
(Isc)
The reinforced breaking capacity due to cascading
in circuit-breaker combinations is maintained.
The worst-case situations have been tested.
Rated insulation voltage
(Ui)
750 V AC
Rated operational voltage
(Ue)
690 V AC
Rated impulse withstand voltage (Uimp) 8 kV
Network frequency
50/60 Hz
Degree of protection
IPxxB
Degree of pollution
3
Overvoltage category
III
Additional technical characteristics
Reference temperature
40 °C
Operating temperature
-25 °C to 55 °C
Linergydistributionsystems
Distribution blocks
LinergyDP
Quick distributionblocks
93