D-6

Electrical diagrams

Electrical interlocking with emergency off by shunt release

DB401809

ATTENTION

(1)

Not to be wired on fixed version.

The diagram shows the electrical wiring for circuit breakers.

When wiring the SDE with

switch-disconnectors, connect

the SDE to terminals 81 and 84.

Legends

QN

“Normal” source Compact NS630b to 1600

QR

“Replacement” source Compact NS630b to 1600

OF...

breaker ON/OFF indication contact

SDE1

“fault-trip” indication contact

CE1

“connected-position” indication contact (carriage switch)

F1

auxiliary power supply circuit breaker

MX

shunt release

BP

emergency off button with latching

KA3

auxiliary relay

ON

“Normal” source opening order

OR

“Replacement” source opening order

FN

“Normal” source closing order (0.25 second delay)

FR

“Replacement” source closing order (0.25 second delay)

MT

Motor Mechanism

States permitted by mechanical interlocking system

Normal

Replacement

0

0

1

0

0

1

Note:

after a fault trip, the breaker must be reset manually by pressing

its reset button.

Diagram shown with circuit breakers in connected position, open,

charged, and ready to close.

Auxiliary power supply = supply voltage of auxiliary relays (KA...)

= supply voltage of electrical auxiliaries (electrical operation,

MCH, MX, MN...).

2 Compact NS630b/1600 devices

Diagram no. 51201181