D-11
Electrical diagrams
Automatic-control system without IVE unit for permanent replacement source
DB401814
ATTENTION
(1)
Not to be wired on fixed version.
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with
switch-disconnectors, connect
the SDE to terminals 81 and 84.
Legends
QN
Normal” source Compact NS630b to 1600
QR
“Replacement” source Compact NS630b to 1600
OF...
breaker ON/OFF indication contact
SDE1
“fault-trip” indication contact
CE1
“connected-position” indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
F2/F3
circuit breaker (high breaking capacity)
S1
control switches
KA1
auxiliary relays - UN presence detection
KA2
auxiliary relays - UR presence detection
KM1
contactors with 0.25 second delay (for transfer
to “Replacement” source)
KM2
contactors with 0.25 second delay (for transfer to “Normal”
source)
MT
Motor Mechanism
States permitted by mechanical interlocking system
Normal
Replacement
0
0
1
0
0
1
Note:
after a fault trip, the breaker must be reset manually by pressing
its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN...).
Remote-operated
source-changeover systems
0
2 Compact NS630b/1600 devices
Diagram no. 51201186