D-11

Electrical diagrams

Automatic-control system without IVE unit for permanent replacement source

DB401814

ATTENTION

(1)

Not to be wired on fixed version.

The diagram shows the electrical wiring for circuit breakers.

When wiring the SDE with

switch-disconnectors, connect

the SDE to terminals 81 and 84.

Legends

QN

Normal” source Compact NS630b to 1600

QR

“Replacement” source Compact NS630b to 1600

OF...

breaker ON/OFF indication contact

SDE1

“fault-trip” indication contact

CE1

“connected-position” indication contact (carriage switch)

F1

auxiliary power supply circuit breaker

F2/F3

circuit breaker (high breaking capacity)

S1

control switches

KA1

auxiliary relays - UN presence detection

KA2

auxiliary relays - UR presence detection

KM1

contactors with 0.25 second delay (for transfer

to “Replacement” source)

KM2

contactors with 0.25 second delay (for transfer to “Normal”

source)

MT

Motor Mechanism

States permitted by mechanical interlocking system

Normal

Replacement

0

0

1

0

0

1

Note:

after a fault trip, the breaker must be reset manually by pressing

its reset button.

Diagram shown with circuit breakers in connected position, open,

charged, and ready to close.

Auxiliary power supply = supply voltage of auxiliary relays (KA...)

= supply voltage of electrical auxiliaries (electrical operation,

MCH, MX, MN...).

Remote-operated

source-changeover systems

0

2 Compact NS630b/1600 devices

Diagram no. 51201186