D-16

Electrical diagrams

Electrical interlocking by IVE unit with lockout after a fault

DB401820

ATTENTION

(1)

Not to be wired for the “without lockout after a fault” solution.

(2)

Not to be wired on fixed version.

(3)

Prefabricated wiring supplied.

(4)

See section “IMPORTANT” here after.

The diagram shows the electrical wiring for circuit breakers.

When wiring the SDE with

switch-disconnectors, connect

wire BK to terminal 82.

IMPORTANT

The relays controlling the “normal” and “replacement”

circuit breakers must be mechanically and/or

electrically interlocked to prevent them from giving

simultaneous closing commands.

Legends

QN

“Normal” source Masterpact NT or NW

QR

“Replacement” source Masterpact NT or NW

MCH

spring-charging motor

MX

standard opening voltage release

XF

standard closing voltage release

OF...

breaker ON/OFF indication contact

SDE1

“fault-trip” indication contact

PF

“ready-to-close” contact

CE1

“connected-position” indication contact (carriage switch)

CH

“springs charged” indication contact

IVE

electrical interlocking and terminal block unit

F1

auxiliary power supply circuit breaker

ON

“Normal” source opening order

OR

“Replacement” source opening order

FN

“Normal” source closing order (0.25 second delay)

FR

“Replacement” source closing order (0.25 second delay)

States permitted by mechanical interlocking system

Normal

Replacement

0

0

1

0

0

1

Note:

diagram shown with circuit breakers in connected position, open,

charged, and ready to close.

Auxiliary power supply = supply voltage of auxiliary relays (KA...)

= supply voltage of electrical auxiliaries (electrical operation,

MCH, MX, MN...).

Wiring colour codes

RD GN BK VT YE GY WH BN

red green black violet yellow grey white brown

2 Masterpact NT or NW devices

Diagram no. 51201142