Table of Contents Table of Contents
Previous Page  162 / 182 Next Page
Information
Show Menu
Previous Page 162 / 182 Next Page
Page Background

D-21

Electrical diagrams

Automatic-control system for permanent replacement source with lockout after a fault (with MN)

DB401825

ATTENTION

(1)

Not to be wired for the “without lockout after a fault” solution.

(2)

Not to be wired on fixed version.

(3)

Prefabricated wiring supplied.

The diagram shows the electrical wiring for circuit breakers.

When wiring the SDE with

switch-disconnectors, connect

wire BK to terminal 82.

Legends

QN

“Normal” source Masterpact NT or NW

QR

“Replacement” source Masterpact NT or NW

MCH

spring-charging motor

XF

standard closing voltage release

MN

undervoltage release

OF...

breaker ON/OFF indication contact

SDE1

“fault-trip” indication contact

PF

“ready-to-close” contact

CE1

“connected-position” indication contact (carriage switch)

CH

“springs charged” indication contact

IVE

electrical interlocking and terminal block unit

F1

auxiliary power supply circuit breaker

F2

circuit breaker (high breaking capacity)

S1

control switches

KA1

auxiliary relays

KA2

auxiliary relays

KA3

auxiliary relays

States permitted by mechanical interlocking system

Normal

Replacement

0

0

1

0

0

1

Note:

diagram shown with circuit breakers in connected position, open,

charged, and ready to close.

Auxiliary power supply = supply voltage of auxiliary relays (KA...)

= supply voltage of electrical auxiliaries (electrical operation,

MCH, MX, MN...).

Wiring colour codes

RD GN BK VT YE GY WH BN

red green black violet yellow grey white brown

Remote-operated

source-changeover systems

2 Masterpact NT or NW devices

Diagram no. 51156904