D-19

Electrical diagrams

Automatic-control system without IVE unit for permanent replacement source with lockout after a fault

DB401823

ATTENTION

(1)

Not to be wired on fixed version.

The diagram shows the electrical wiring for circuit breakers.

When wiring the SDE with

switch-disconnectors, connect

the SDE to terminals 81 and 84.

Legends

QN

“Normal” source Masterpact NT or NW

QR

“Replacement” source Masterpact NT or NW

MCH

spring-charging motor

MX

standard opening voltage release

XF

standard closing voltage release

OF...

breaker ON/OFF indication contact

SDE1

“fault-trip” indication contact

PF

“ready-to-close” contact

CE1

“connected-position” indication contact (carriage switch)

CH

“springs charged” indication contact

F1

auxiliary power supply circuit breaker

F2/F3

circuit breaker (high breaking capacity)

S1

control switches

KA1

auxiliary relays - UN presence detection

KA2

auxiliary relays - UR presence detection

KM1

contactors with 0.25 second delay (for transfer to

“Replacement” source)

KM2

contactors with 0.25 second delay (for transfer to “Normal”

source)

States permitted by mechanical interlocking system

Normal

Replacement

0

0

1

0

0

1

Note:

diagram shown with circuit breakers in connected position, open,

charged, and ready to close.

Auxiliary power supply = supply voltage of auxiliary relays (KA...)

= supply voltage of electrical auxiliaries (electrical operation,

MCH, MX, MN...).

Remote-operated

source-changeover systems

2 Masterpact NT or NW devices

Diagram no. 51156226