Table of Contents Table of Contents
Previous Page  143 / 182 Next Page
Information
Show Menu
Previous Page 143 / 182 Next Page
Page Background

D-2

Electrical diagrams

Source-changeover system without automatic-control system

Without auxiliaries for emergency off

Local reset

DB401805

DB101659

Voluntary remote reset

DB101660

Automatic reset

(1)

Prefabricated wiring: cannot be modified.

Legends

QN

“Normal” source Compact NSX equipped with motor mechanism

QR

“Replacement” source Compact NSX equipped with motor

mechanism

SDE

“fault-trip” indication contact

IVE

electrical interlocking and terminal block unit

MT

motor mechanism

OF2

breaker ON/OFF indication contact

RN

reset order for breaker QN

RR

reset order for breaker QR

States permitted by mechanical interlocking system

Normal

Replacement

0

0

1

0

0

1

Note:

diagram shown with circuits de-energised, circuit breakers open

and relays in normal position.

2 Compact NSX100/630 devices

Diagram no. 51201177