Table of Contents Table of Contents
Previous Page  144 / 182 Next Page
Information
Show Menu
Previous Page 144 / 182 Next Page
Page Background

D-3

Electrical diagrams

Source-changeover system without automatic-control system

With emergency off by MN release and automatic reset

DB401806

Automatic reset

(1)

Prefabricated wiring supplied.

(2)

Independent auxiliary source.

Legends

QN

“Normal” source Compact NSX equipped with

motormechanism

QR

“Replacement” source Compact NSX equipped with motor

mechanism

MN

undervoltage release

OF2

breaker ON/OFF indication contact

SDE

“fault-trip” indication contact

MT

motor mechanism

IVE

electrical interlocking and terminal block unit

BP

emergency off button with latching

KA3

auxiliary relay

F1

auxiliary power supply circuit breaker

States permitted by mechanical interlocking system

Normal

Replacement

0

0

1

0

0

1

Note:

after a fault trip, the breaker must be reset manually by pressing

its reset button.

Diagram shown with circuits de-energised, circuit breakers open

and relays in normal position.

Remote-operated

source-changeover systems

2 Compact NSX100/630 devices

Diagram no. 51201178