6/4
Technical
Section 11
Dimensions
Section 12
6
DB123517
b
b
Operating state
indicator lamp
b
b
Pushbutton for:
v
v
"mode" selection
v
v
opening/closing
manual control
Operating modes
Mode 1: Reflex iC60 opening/closing,
locally or centrally controlled
b
b
The opening/closing orders come from various control
points, and they are taken into account in their order of arrival
v
v
Y1: latched order local control
v
v
Y2: impulse-type local control
v
v
Y3: latched order centralized control
Mode 2: Reflex iC60 opening/closing,
possible inhibition of local impulse-type
control
b
b
Y1 is used to inhibit Y2
v
v
Y1: local opening/Y2 inhibition latched order control
v
v
Y2: impulse-type local opening/closing control
v
v
Y3: latched order centralized opening/closing control
Mode 3: Reflex iC60 opening/closing,
possible inhibition of centralised latched
order control
b
b
Y1 is used to inhibit Y3
v
v
Y3 inhibition local latched order control
v
v
Y2: impulse-type local opening/closing control
v
v
Y3: latched order centralized opening/closing control
Table of modes
Mode 1
Mode 2
Mode 3
Reflex iC60 with interface Ti24
b
b
Possible mode
b
b
Possible mode
b
b
Default mode
Three types of control: Y1, Y2, Y3
DB124370
N P
PN
24V
auto/
OFF
0V
Y3
Y3
Ti24
Y1 Y2
11 12 14
O/C
21 22 24
auto/OFF
auto/OFF
Reflex iC60
N P
24V
24V
230V
Ti24
Y1 Y2
11 12 14
O/C
21 22 24
Reflex iC60
Zone 1
Zone 2
Y2 Y1
Y2 Y1
O/C
auto/
OFF
0V O/C
Reflex iC60 with Ti24 interface
DB124372
Mode 1
Mode 2
Mode 3
N P
PN
24 V
c
24V
0 V
PLC
In In
Out
Y3
Ti24
Y1 Y2
11 12 14
Reflex iC60
230V
auto/
OFF 0V
O/C
21 22 24
auto/OFF
O/C
Y2 Y1
Centralized
control
(PLC)
Remote control is possible by 3 operating modes to be set using the pushbutton on
the front panel.
Reflex iC60H
(curves B, C, D) (cont.)
Control, remote control
Integrated control circuit
breakers