6/6
Technical
Section 11
Dimensions
Section 12
6
DB123310
DB123312
DB123314
IP20
IP40
Clip on DIN rail 35 mm.
Indifferent position of installation.
Technical data
Control circuit
Supply voltage (Ue) (N/P)
230 V AC - 50 Hz
Control voltage (Uc)
Inputs (Y1/Y2)
230 V AC - 5 mA
(24…48 V AC/DC, with iMDU auxiliary)
Input (Y3)
24 V DC - 5.5 mA
Min. duration of control impulse (Y2)
u
250 ms
Response time (Y2)
y
200 ms
Consumption
y
1 W
Inrush consumption
< 1000 VA
Length of control wires
Inputs (Y1/Y2)
Cable: 100 m
Wires in a sheath: 500 m
Input (Y3)
500 m
Inrush current at
230 V - 50 Hz
2P
4.2 Â
3P
8.2 Â
4P
16.2 Â
Power circuit
Max. working voltage (Ue)
400 V AC
Insulation voltage (Ui)
500 V
Rated impulse withstand
voltage (Uimp)
Set to Disconnected 6 kV
Set to Ready
4 kV
Thermal tripping
Reference
temperature
50°C
Magnetic tripping
Curve B
4 In ± 20 %
Curve C
8 In ± 20 %
Curve D
12 In ± 20 %
Overvoltage category (IEC 60364)
IV
Temperature derating
See module CA908007
Indication / Remote control
Potential-free changeover
contact outputs
(O/C, auto/OFF)
Min.
24 V DC - 100 mA
Max
230 V AC - 1 A
Ti24 interface (as per IEC 61131)
Outputs (O/C, auto/OFF)
Ti24 interface
24 V DC - 100 mA max
Endurance (O-C)
Electrical
AC1 - AC7a
Up to 50,000 cycles
(1)
AC5a - AC5b
Up to15,000 cycles
(1)
AC7c
Up to 20,000 cycles
(1)
Mechanical
50,000 cycles
Additional characteristics
Degree of protection
(IEC 60529)
Device only
IP20
Device in a modular
enclosure
IP40
Insulation class II
Degree of pollution
3
Operating temperature
-25°C to +60°C
Storage temperature
-40°C to +85°C
Tropicalization
Treatment 2
(relative humidity of 93 % at 40°C)
Immunity to voltage dips
IEC 61000-4-11 class III
Immunity to power supply frequency variations
IEC 61000-4-28 and IACS E10
Immunity to harmonics
IEC 61000-4-13 class 2
Immunity to electrostatic
discharges
Air
8 kV, IEC 61 000-4-2
Contacts
4 kV, IEC 61 000-4-2
Immunity to stray magnetic fields
10 V/m up to 3 GHz, IEC 61000-4-3
Immunity to fast transients
4 kV from 5 to 100 kHz, IEC 61000-4-4
Immunity to shock waves
IEC 61000-4-5
Immunity to power frequency magnetic fields
10 V from 150 kHz to 80 MHz,
IEC 61000-4-6
Immunity to grid frequency magnetic fields
Level 4 30 A/m to IEC 61000-4-8 and
IEC 61000-4-9
Conducted emissions
CISPR 11/22
Radiated emissions
CISPR 11/22
(1) See the derating table according to the load types and ratings
Reflex iC60H
(curves B, C, D) (cont.)
Control, remote control
Integrated control circuit
breakers