ARA automatic reclosers (cont.)

For iC60 circuit breakers

and iID residual current circuit breakers

Control

Remote control

Operating principle

The ARA automatic recloser makes a number of attempts at reclosing depending on

the program chosen by the user.

The program includes the following settings:

b

b

A time delay before reclosing (TA).

b

b

A reinitialization time delay (TB).

b

b

A maximum number of reclosing attempts.

If, following these attempts, the fault is still present, the device places itself in

waiting for manual reclosing, or final remote reclosing (Y2).

ARA iC60

Number of

reclosing

attempts

Delay

before

reclosing

Check time Final

reclosing Y2

TA

TB

Program

2

1

3 4

1

60 s

6 min.

Once after

inhibition

2

1

3 4

3

60 s

3 min.

3 min.

2 min.

6 min.

6 min.

2 1

3

4

5

60 s

3 min.

3 min.

3 min.

3 min.

2 min.

6 min.

6 min.

6 min.

6 min.

2 1

3

4

5

60 s

3 min.

4 min.

5 min.

6 min.

2 min.

6 min.

8 min.

10 min.

12 min.

ARA iID

Number of

reclosing

attempts

Delay

before

reclosing

Check time Final

reclosing Y2

TA

TB

Only 1 program

available

15

20 s

40 s

3 min.

3 min.

...

30 min.

30 min.

...

Once per cycle

DB124061

DB124062

DB124063

DB124064