6

ARA automatic reclosers

For iC60 circuit breakers

and iID residual current circuit breakers

Control

Remote control

The ARA reclosing auxiliary can:

b

b

Perform automatic reclosing of the associated protection device, after tripping.

b

b

Increase the availability of installations without supervision, isolated, hard of

access and demanding very great availability (mobile telephony systems,

motorways, pumping stations, airports, railways, meteorological stations, service

stations, automatic teller machines, public lighting, tunnels, etc.), by restoring

them to operation without intervention by personnel in the event of a transient

fault (atmospheric disturbances, industrial overvoltages, etc.).

b

b

For the ARA iC60, the operator can choose predefined reclosing program which

allows the safety and availability of facilities to be reconciled taking into account

the facility's environment.

b

b

The circuit is placed in safety configuration by the padlocking device.

Catalogue numbers

ARA iC60

For circuit breaker

Width in 9 mm

modules

1P, 1P+N, 2P

Number of

programs

Voltage

4

230 V AC, 50/60 Hz

A9C70132

7

3P, 4P

4

230 V AC, 50/60 Hz

A9C70134

7

ARA iID

For residual current circuit breaker

Width in 9 mm

modules

2P

Number of

programs

Voltage

1

230 V AC, 50/60 Hz

A9C70342

7

4P

1

230 V AC, 50/60 Hz

A9C70344

7

Auxiliaries

See module CA907000 and CA907002

Diagram

22 21

OF

24 14 1112

N P

Y2 Y1

ARA

Locked

Legend

Type

Application

2

1

3 4

Choice of program (ARA iC60)

Y1

"Remote" inhibition of automatic reclosing

Y2

Remote control of final reclosing

N

230 V power supply

P

Locked

21 22 24

Automatic recloser inhibition indication contact

OF

11 12 14

Indicates the state of the circuit breaker or residual current

circuit breaker (opened or closed)

Indicator

lamp

Flashing green

ARA automatic recloser operational

Flashing red

Reclosing cycle in progress

Fixed red

ARA automatic recloser locked at end of reclosing

cycle: circuit breaker or residual current circuit

breaker tripped (open)

Flashing orange

ARA automatic recloser not operational

DB124060

DB123582

ARA iC60

DB123583

DB406179

ARA iID

230 V

iC60 or iID

DB124061

ARA iC60

ARA iID

PB106256-40

DB124065

PB106257-40

Technical

Section 11

Dimensions