Background Image
Table of Contents Table of Contents
Previous Page  112 / 408 Next Page
Information
Show Menu
Previous Page 112 / 408 Next Page
Page Background

6

6/2

Technical

Section 11

Dimensions

Section 12

Reflex iC60H

(curves B, C, D)

Control, remote control

Integrated control circuit

breakers

PB106239-40

PB106238-40

Catalogue numbers

Reflex iC60 circuit breaker

Type

2P

3P

4P

Rating (In)

Curve

Curve

Curve

B

C

D

B

C

D

B

C

D

Reflex iC60H

With Ti24 interface

10 A

A9C64210 A9C65210 A9C66210 A9C64310 A9C65310 A9C66310 A9C64410 A9C65410 A9C66410

16 A

A9C64216 A9C65216 A9C66216 A9C64316 A9C65316 A9C66316 A9C64416 A9C65416 A9C66416

25 A

A9C64225 A9C65225 A9C66225 A9C64325 A9C65325 A9C66325 A9C64425 A9C65425 A9C66425

40 A

A9C64240 A9C65240 -

A9C64340 A9C65340 -

A9C64440 A9C65440 -

Width in 9 mm modules

9

11

13

The Reflex iC60 devices are integrated control circuit breakers which combine the

following main functions in a single device:

b

b

Remote control by latched and/or impulse-type order according to the 3 operating

modes to be chosen by the user.

b

b

Circuit breaker, to provide:

v

v

circuit protection against short-circuit currents,

v

v

circuit protection against overload currents,

v

v

disconnection in the industrial sector.

Resetting after a fault is performed manually, by the resetting handle.

The version with Ti24 allows direct interfacing of the Reflex iC60 with a PLC, to:

b

b

Execute remote control (Y3).

b

b

Indicate the state of the control circuit (O/C) and circuit-breaker state information

(auto/OFF).

The Ti24 interface also allows fast, reliable connection of the Reflex iC60 to the

Acti 9 Smartlink thanks to the prefabricated cables.

The iMDU auxiliary allows the Reflex iC60 to be controlled in 24/48 V AC/DC.

IEC/EN 60947-2

Alternating current (AC) 50 Hz

Ultimate breaking capacity (Icu) as per IEC/EN 60947-2

Service

breaking

capacity (Ics)

Voltage (Ue)

Ph/Ph (2P, 3P, 4P)

220 to 240 V

380 to 415 V

Reflex iC60H

Rating (In)

10 to 40 A 30 kA

15 kA

50 % of Icu