Background Image
Table of Contents Table of Contents
Previous Page  109 / 408 Next Page
Information
Show Menu
Previous Page 109 / 408 Next Page
Page Background

5/13

5

RED

A type

30mA (cont.)

Protect

Earth leakage protection

Automatic recloser

DB123310

DB123312

Dimensions (mm)

DB109809

Weight (g)

Recloser

RED

350

Technical data

Main characteristics

RED 25...63 A A type

Earthing grounding systems

TT and TN-S only

Impulse withstand voltage (Uimp)

4 kV

Insulation voltage (Ui)

500 V

8/20 μs wave immunity level

250 Â

Tropicalisation

Treatment 2 (relative humidity: 95 % at 55°C)

Operating temperature

-5°C to +40°C

Storage temperature

-20°C to +60°C

Protection class

IP20 at terminals

Additional characteristics

Residual current device

Making and breaking capacity, rated residual

current (I

Δ

m = Im)

630 A

Breaking capacity in association with

protection device

6000 A (gL 63 A)

Tripping time

I

Δ

n:

y

300 ms

5 I

Δ

n:

y

40 ms

Number of cycles (O-C)

Mechanical: 1 000

Fixed sensitivity releases for all ratings

Instantaneous release

Test button min operating voltage

100 V

Recloser

Max duration of a restart cycle

90 s

Number of restart operations

15/hour

Maximum number of consecutive restart

attempts (if no earth fault)

3

Min interval between 2 closings

180 s

Insulation fault presence monitoring

Yes

Restart in event of transient insulation fault

Yes

Stopping restart cycle if insulation fault

present

Yes

Not operating resistance to earth (Rd)

20 k

Ω

Operating resistance to earth (Rdo)

70 k

Ω

Power consumed by the electronics

S = 0 VA

Indication

RED status indication

Mechanical:

by O-l (open-closed) 2-position lever

Electrical:

by 1 red indicator light on the front panel

IP20

IP40

Clip on DIN rail 35 mm.

Indifferent position of installation.

Technical

Section 11

Dimensions

Section 12