Operation

Recloser

The built-in automatic recloser automatically recloses the residual current device

after checking insulation of the downstream circuit.

If the resistance to earth is lower than Rd, then RED reclosing is prohibited.

If the resistance to earth is higher than Rdo, then RED reclosing is allowed.

Residual current device

The RED operate in the residual current device mode, without automatic restart,

when the sliding cover is open, i.e. to the right in the Auto Off position (Fig. 1).

The automatic restart mode and the Autotest are activated, when the sliding cover is

closed, i.e. to the left in the Auto On position (Fig. 2).

Test

b

b

Supply from

above or below

b

b

Test button

d

This is onlypossible inmanualmode, i.e. slidingcover open in theAutoOff

position. You can thenmanually test thedevicebypressing theTest key.

Thedownstream installation is then temporarilybroken. Youmust then

manually reclose theREDby activating theO-l lever topower supply the

downstreamcircuit.

Fig. 1

Fig. 2

RED

A type

30mA (cont.)

Protect

Earth leakage protection

Automatic recloser