5/9
Technical
Section 11
Dimensions
Section 12
5
RED
A type
30mA
Protect
Earth leakage protection
Automatic recloser
PB101779_SE-50
DB404503
The RED
RE
sidual current
D
evice recloser, is made up of a residual current device
and a recloser.
b
b
protection of people against direct and indirect contacts
b
b
protection of installations against insulation faults
b
b
disconnection of on-load electric circuits, already protected against overloads
and short-circuits
b
b
automatic restart after insulation monitoring of the downstream circuit.
IEC 61008, EN 61008
DB116619
18681
Circuit-breaker
(MCB) or Fuse (FU)
Catalogue numbers
Residual current circuit breaker RED
Type
Width in mod.
of 9 mm
2P
Sensitivity 30 mA
DB122882
Rating 25 A
18693
8
40 A
18695
Voltage rating (Ue)
230 V
Frequency rating
50 Hz
Coordination table, max short-circuit current (kA rms)
Circuit-breakers, fuse / RED type A
Circuit-breakers
Fuse
C32 K60 DT40 DT40N C60 C120 NG125 gL 63
RED A Type
Network
230 V
L/N
25 A
4.5 6
6
6
6
6
6
6
40 A
4.5 6
6
6
6
6
6
6