Background Image
Table of Contents Table of Contents
Previous Page  105 / 408 Next Page
Information
Show Menu
Previous Page 105 / 408 Next Page
Page Background

5/9

Technical

Section 11

Dimensions

Section 12

5

RED

A type

30mA

Protect

Earth leakage protection

Automatic recloser

PB101779_SE-50

DB404503

The RED

RE

sidual current

D

evice recloser, is made up of a residual current device

and a recloser.

b

b

protection of people against direct and indirect contacts

b

b

protection of installations against insulation faults

b

b

disconnection of on-load electric circuits, already protected against overloads

and short-circuits

b

b

automatic restart after insulation monitoring of the downstream circuit.

IEC 61008, EN 61008

DB116619

18681

Circuit-breaker

(MCB) or Fuse (FU)

Catalogue numbers

Residual current circuit breaker RED

Type

Width in mod.

of 9 mm

2P

Sensitivity 30 mA

DB122882

Rating 25 A

18693

8

40 A

18695

Voltage rating (Ue)

230 V

Frequency rating

50 Hz

Coordination table, max short-circuit current (kA rms)

Circuit-breakers, fuse / RED type A

Circuit-breakers

Fuse

C32 K60 DT40 DT40N C60 C120 NG125 gL 63

RED A Type

Network

230 V

L/N

25 A

4.5 6

6

6

6

6

6

6

40 A

4.5 6

6

6

6

6

6

6