Operation ON mode: temporary network fault

REDs, REDtest

LED 1

LED 2

The built-in automatic recloser automatically recloses the residual current device

after checking insulation of the downstream circuit.

Rd: lower level of insulation resistance, if R<Rd = no reclose

Rdo: higher level of insulation resistance, if Rd>Rdo = reclose

1

0

1

0

1

0

t=5s

t<2s

LED 2

LED 1

<10s

*

t=5s

1

0

Test

Default

DB404529

Operation ON mode: long network fault

REDs

If the circuit is faulty, the switch is prohibited from reclosing. After a time delay of

15 minutes, the downstream circuit insulation is rechecked.

There are then two possibilities:

b

b

the installation is still faulty (the resistance to earth is lower than Rd): in this case

a new check will be carried out in 15 minutes.

b

b

the fault was temporary and has disappeared (the resistance to earth is higher

than Rdo): the recloser automatically recloses the REDs.

I

Δ

n

30 mA

300 mA

Rd

8 k

2.5 k

Rdo

16 k

5 k

1

0

1

0

1

0

LED 2

LED 1

< 3min

*

t=5s

t=15min

t

y

15min

t=5s

t=5s

1

0

Test

Default

(*) Reclosing time.

(*) Reclosing time.

REDs, REDtest (cont.)

Protect

Earth leakage protection

Automatic recloser