Operation ON mode: temporary network fault
REDs, REDtest
LED 1
LED 2
The built-in automatic recloser automatically recloses the residual current device
after checking insulation of the downstream circuit.
Rd: lower level of insulation resistance, if R<Rd = no reclose
Rdo: higher level of insulation resistance, if Rd>Rdo = reclose
1
0
1
0
1
0
t=5s
t<2s
LED 2
LED 1
<10s
*
t=5s
1
0
Test
Default
DB404529
Operation ON mode: long network fault
REDs
If the circuit is faulty, the switch is prohibited from reclosing. After a time delay of
15 minutes, the downstream circuit insulation is rechecked.
There are then two possibilities:
b
b
the installation is still faulty (the resistance to earth is lower than Rd): in this case
a new check will be carried out in 15 minutes.
b
b
the fault was temporary and has disappeared (the resistance to earth is higher
than Rdo): the recloser automatically recloses the REDs.
I
Δ
n
30 mA
300 mA
Rd
8 k
Ω
2.5 k
Ω
Rdo
16 k
Ω
5 k
Ω
1
0
1
0
1
0
LED 2
LED 1
< 3min
*
t=5s
t=15min
t
y
15min
t=5s
t=5s
1
0
Test
Default
(*) Reclosing time.
(*) Reclosing time.
REDs, REDtest (cont.)
Protect
Earth leakage protection
Automatic recloser