25
Cat. Nos. 0390 71/72/73/74
Viking 3
heavy duty terminal blocks
A
B'
C
B
A min.
A max.
E
C
H
G
F
D
mm
2
35
70
95
120
150
185
300
AWG
2
00
0000
250
300
350
600
Cable section equivalence table
■
Characteristics of heavy duty plate terminal blocks
■
Separation barriers
Dimensions (mm)
IEC EN 60947-7-1
Fire resistance:
960°C, IEC EN 60695-2-11
V2 according to UL 94
Insulating material: polyamide - 30 °C
to + 100 °C
Cat. Nos. 0390 31/32/33/34
Voltage (V) Intensity (A)
Cat. Nos.
IEC
IEC
0390 31/71
1000
125
0390 32/72
1000
192
0390 33/73
1000
269
0390 34/74
1000
415
Dimensions (mm)
Dimensions (mm)
Cat. Nos.
A max. A min.
B
C
D
E
F
G
H
0390 13
227
155
36
82
73
88
176
185
191
0390 10/14/17/20
296
200
42
83 . 5
74 . 5
89 . 5
212
221
227
0390 11/15/18/21
337
216
55
107 . 3 98 . 5 113 . 5
257
266
272
B
A
Cat. Nos. A
B Thickness
0394 77
106
82 8
0394 78
188
102 12
Cat. Nos. 0394 77/78
Cat. Nos.
A
B B'
C
0390 31
M 8
56
84
0390 32
M 10 61
84
0390 33
M 10 61
84
0390 34
M 12 64
86
0390 71
M 8
55 . 3
84
0390 72
M 10
60 . 4
84
0390 73
M 10
60 . 4
84
0390 74
M 12
63 . 5
86
C
A
B
■
Characteristics of heavy duty terminal blocks for copper
and aluminium cables
IK 04
Conform to IEC 60947-7-1, EN 60947-7-1
UL 1059 and 486 E - CSA 22-2
Fire resistant IEC 60695-2-11: 960°C (except cover)
V2 according to UL 94
Insulation voltage Ui: 1000 V
Impulse voltage Uimp: 12 kV
Insulating material:
- polyamide body - 30 °C to + 100 °C
- polypropylene cover - 25 °C to + 100 °C
Connection table
Currents table
Terminal for cable lug - cable Cable - terminal for cable lug
Cable - cable
Terminal for cable lug -
terminal for cable lug
Cat. Nos.
Connection
Width of Screw Connection
Width of Screw Width
(mm
2
)
plate (mm)
Ø
(mm
2
)
plate (mm)
Ø
(mm)
Cable - Cable
0390 10
Rigid or flexible
Rigid or flexible
42
Cu/Al: 35 to 120
Cu: 35 to 70
0390 11
Rigid or flexible
Rigid or flexible
55
Cu/Al: 70 to 300
Cu: 70 to 150
Terminal for cable lug - Terminal for cable lug
0390 13
Cu/Al: max. 95
28
M 8 Cu/Al: max. 95
28
M 8
36
0390 14
Cu/Al: max. 150
34
M 10 Cu/Al: max. 150
34
M 10
42
0390 15
Cu/Al: max. 300
46
M 12 Cu/Al: max. 300
46
M 12
55
Terminal for cable lug - Cable
0390 17
Cu/Al: max. 150
34
M
10
Rigid or flexible
42
Cu: 35 to 95
0390 18
Cu/Al: max. 300
46
M
12
Rigid or flexible
55
Cu: 70 to 150
Cable - Terminal for cable lug
Rigid or flexible
0390 20
Cu: 35 to 120
Cu/Al: max. 120
34
M 10
42
Al: 35 to 120
Cu/Al: max. 70
34
M 10
42
Rigid or flexible
0390 21
Cu: 70 to 300
Cu/Al: max. 300
46
M 12
55
Al: 70 to 300
Cu/Al: max.150
46
M 12
55
Cat. Nos.
Current (A)
Short-circuit
Tightening torque
Width
current (kA)
(Nm)
Shunted
I/O
Shunted
I/O
Site
Factory
(mm)
input
currents
input
IEC
IEC CSA UL
Cable - Cable
0390 10
340
250 200 170
14 . 4
8 . 4
15
15
42
0390 11
570
400 300 285
36
18
35
35
55
Terminal for cable lug - Terminal for cable lug
0390 13
310
310 250 230
11 . 4
11 . 4
15
15
36
0390 14
415
415 340 285
18
18
15
15
42
0390 15
670
670 520 420
36
36
35
35
55
Terminal for cable lug - Cable
0390 17
415
315 210 230
18
11 . 4
15
15
42
0390 18
670
420 325 285
36
18
35
35
55
Cable - Terminal for cable lug
0390 20
340
340 235 255
14 . 4
8 . 4
15
15
42
0390 21
570
570 375 420
36
18
35
35
55
Shunts
0394 46
450 max.
6
0394 47
700 max.
10