95

n

Feeder lengths

3 000 (L)

Dimension H changes with the rating, and is specified on p. 112-117

10

H

3 000 (L)

10

H

Minimum and maximum dimensions of single and double bars

Aluminium

630 A to 4000 A

Copper

800 A to 5000 A

(L) min./max. (mm)

1000 / 3000

n

Distribution lengths

Dimension H changes with the rating, and is specified on p. 112-117

Minimum and maximum dimensions of single and double bars

Aluminium

630 A to 4 000 A

Copper

800 A to 5000 A

(L) min./max. (mm)

1000 / 3000

3 000 (L)

650

850

850

650

10

H

n

Expansion lengths

Absorb the thermal expansion during normal use

that, on long runs, would otherwise cumulate and

put abnormal force on the connection points

Expansion lengths should be placed

in straight runs of more than 40 m

and repeated every 40 m

e.g. 70 m straight section

should contain 1 expansion

length in the middle

e.g. 120 m straight section should

contain 2 expansion lengths, spaced

every 40 m

All dimensions (mm) are nominal

n

Transposition lengths

1 2 3 N

N 1 2 3

N 1 2 3

N 3 1 2

N 1 2 3

N 3 1 2

1200

10

H

Phase transposition

1 2 3 N

N 1 2 3

N 1 2 3

N 3 1 2

1 2 3 N

N 1 2 3

N 1 2 3

N 3 1 2

10

1000

H

Neutral rotation

175

n

End stops

Maintain IP 55 protection at the end of a run

In runs exceeding 100 m it is recommended to include two transposition

lengths to balance mutual phase reactance and electric impedance

(one at 1/3 and one at 2/3 distance of the run)

Dimension H changes with the rating and is specified on p. 112-117

Neutral rotation can be used when the sequence of the distribution

board phases is different to that of the transformer