Background Image
Table of Contents Table of Contents
Previous Page  90 / 132 Next Page
Information
Show Menu
Previous Page 90 / 132 Next Page
Page Background

SCP

super compact busbar

technical information

90

n

Harmonics

In a distribution system, currents and voltages should have a perfectly

sinusoidal shape. However, in practice the equipment contains electric

devices such as changeover devices or dimmers that make the load

not linear

The currents absorbed, although at regular intervals and with

frequencies equal to that of the rated voltage, sometimes have a

non-sinusoidal wave form, which has the following negative effects :

•worsening of the power factor

•heating of the neutral

•additional losses in electric machinery (transformers and motors)

•instable operation of the protection elements (thermal magnetic and

earth leakage circuit breakers)

In industrial plants these conditions have been occurring for a long

time. However, they are now occurring more and more in service sector

distribution systems, where, from backbone distribution (which uses

3 phase lines), single phase loads are often distributed, which

contributes to increasing the unbalance of the electric system

Each type of non-sinusoidal periodical wave may be split into a more or

less large number of sinusoids (called harmonic components)

A deformed current at a frequency of 50 Hz, like the example

represented by the magenta line on the figure, consists of many

sinusoidal currents with frequency of 50 Hz (fundamental), 100 Hz

(second harmonic component), 150 Hz (third harmonic), and so on

The presence of current harmonics represents an important problem,

causing overload conditions both on phase conductors, and on any

neutral conductor, and results in the reduction of the conductor’s

permitted load

Note

200% neutral versions are available for systems with harmonics present on the neutral

Choice of rating when in the presence of harmonics

When in the presence of harmonics, and when using the chosen Int

rated current, the SCP busbar to be used shall have the rating specified

in the table below

u

t

Fundamental (50 Hz)

Third harmonic (150 Hz)

Fifth harmonic (250 Hz)

Resulting wave shape

100%

23%

11%

50 100 200 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000

250

150

Hz

THD% = 100

H

h = 2

U

h

U

1

( )

2

23

100

( )

2

+

11

100

( )

2

= 100

= 25.5 %

Total distortion (THD) = 25.5%

Distortion of the individual harmonics

Measurement of harmonic distortion

carried out with a network analyser

Rated

current (A)

630 A 800 A 1000 A 1250 A 1600 A 2000 A 2500 A 3200 A 4000 A 5000 A

SCP busbar to be used

THD

15%

630

800 1 000 1 250 1 600 2 000 2 500 3 200 4 000 5 000

15% < THD

33%

800 1 000 1 250 1 600 2 000 2 500 3 200 4 000 5 000

THD > 33%

1 000 1 250 1 600 2 000 2 500 3 200 4 000 5 000