Background Image
Table of Contents Table of Contents
Previous Page  118 / 132 Next Page
Information
Show Menu
Previous Page 118 / 132 Next Page
Page Background

118

Number of poles

3-4

3-4

Nominal rating In (A)

125

160

Rated operating voltage Ue (50-60 Hz)

±

500

500

Rated operating voltage Ue = (V)

250

250

Rated insulation voltage Ui

±

(V)

500

500

Rated impulse withstand voltage Uimp (kV)

6

6

Category of use

A

A

Ultimate breaking capacity (kA) 230 V

±

22

40

400 V

±

16

25

440 V

±

10

20

480/500 V

±

8

10

600 V

±

690 V

±

250 V

=

16

25

Standard breaking capacity Ics (% Icu)

100

100

Rated closing capacity on short-circuit (400 V

±

)

32

52·5

Rated short-time withstand current Icw (kA)

Endurance (o.c. cycle)

mechanical

25000

20000

electrical

8000

8000

Isolation capability

DPX 125

DPX-E

(16 kA)

DPX

(25 kA)

DPX 160

TyPE of cAsE AnD sizE

TyPE of MccB

ElEcTricAl chArAcTErisTics conforMing To En 60947-2

TyPE of ProTEcTion

DiMEnsions AnD wEighTs

Thermal-magnetic release

Earth leakage modules

underneath

side by side

single pole

Dimensions (L x H x D) (mm) triple pole

75·6 x 120 x 74

90 x 150 x 74

four pole

101 x 120 x 74

120 x 150 x 74

Weight (kg)

triple pole

1

1·2

four pole

1·2

1·6

Allen key size (mm) A/F (screw size)

4

6 (M8)

DPX

®

MCCBs

selection chart