121

DPX

®

125

026002-34795u.eps

In 3 A

In 1 A

In 0 . 3 A

b

a

0 . 01

0 . 01

0 . 02

0 . 05

0 . 1

0 . 2

0 . 5

1

2

t (s)

5

10

0 . 05 0 . 1 0 . 5 1

5 10 50 100 300

I (A)

In 0 . 03 A

025049-34794u.eps

Icc (A)

10

10

10

9

10

8

10

7

10

6

10

5

10

4

10

3

10

2

10

1

I

2

t

(A

2

s

)

10

0

10

1

10

2

10

3

10

4

10

5

16

25

40

63

100

125

n

Current limitation curves

10000

1000

100

10

1

0 . 01

0 . 001

0 . 1

t(s)

1

3 2

4 5 10 20 30 50 100

I/In

1

2

125 A

100 A

63 A

40 A

25 A

16 A

025604-34792u.eps

025049-34793u.eps

0 . 9

0 . 8

0 . 7

0 . 3

0 . 25

0 . 2

Icc (kA)

10

0

10

0

10

1

10

2

10

3

2 3 4 5

2 3 4 5

10

1

10

2

2

3

4

5

2

3

4

5

2

3

4

5

IP (kA)

DPX125 25 kA

DPX125 36 kA

100 - 125 A

40 - 63 A

16 A - 25 A

0 . 5

1

2

n

Thermal stress limitation curves

n

Differential tripping curves

at ambient

θ

= 40 °C

I = actual current

Ir = max. adjustment current of thermal release

= thermal release zone when cold

= thermal release zone when hot (in steady state)

Icc = prospective short-circuit symmetrical current

(rms values in A)

I

2

t = limited thermal stress (in A

2

s)

I

(A) = earth leakage current

I

n = nominal earth leakage current

a = instantaneous tripping point

b = 3 possible delay settings (0·3, 1 and 3 seconds)

Icc = prospective short-circuit symmetrical current

(rms values in kA)

IP = maximum peak value (kA)

= current, max. peak, short-circuit rms

= current, unlimited peak (max.), corresponding to power factors shown above (0·15 to 0·9)

Fixed magnetic threshold (Im) (A)

(1)

for DPX 125

In (A)

16

25

40

63

100

125

Phase

480

625

800

950

1250

1 250

N

480

625

800

950

950

950

n

Tripping curves

Nominal breaking capacity (kA) (BS EN 60947-2)

DPX 125 25 kA DPX 125 36 kA

Ue

Icu (kA) Ics (%Icu)

Icu (kA) Ics (%Icu)

400 V

±

25 50

36 75

230 V

±

35 50

40 75

n

Electrical characteristics

Nominal current (In) at 40 °C (A) for DPX 125

In (A)

16

25

40

63

100

125

Phase

16

25

40

63

100

125

N

16

25

40

63

100

125

N/2

63

63

Maximum nominal operating function

500 V

±

- 250 V

=

Nominal frequency

50/60 Hz

Category of use

A

Thermal adjustment

0·7 to 1 In

Maximum permitted cross sections

stranded cables : 70 mm

2

for integral cage terminals

flexible cables : 50 mm

2

copper bar (width) : 12 mm

(1) Trip current for 50/60 Hz

For direct current, multiply by 1·5