1.64

Data is subject to errors and technical modifications.

Standard CT to Plug-in Adaptor - JFA03

Technical Data

Commercial

Distribution

Standard CT to plug-in Adaptor

The

JFA03

converter allows for the connection of up to three standard current

transformers, or standard split-core current transformers (with 1A or 5A

secondary’s), to the plug-in system.

The unit has integrated protection circuitry allowing for disconnection from

meter under load conditions for maintenance.

Important Note

This converter does not provide electrical isolation.

Current transformer secondaries may not be earthed and should be wired as

shown.

Technical Specification

Burden:

<2VA per channel (5A Version)

<0.5VA per channel (1A Version)

Accuracy:

0.4%

Suggested Cable Size:

1.5mm

2

or 2.5mm

2

(2.5mm

2

Max.)

(CT to Adaptor)

Mounting:

DIN rail 35mm

Termination:

CT to adaptor - Rising clamp

screw terminals

Adaptor to Meter - RJ45 Patch Cable

Operating Temperature:

–10°C…+45°C

Storage Temperature:

–25°C…+70°C

Dimension Diagrams (mm)

53

58

90

45

5A or 1A secondary

330mV

CT 1

S1

S1

S1

S2

S2

S2

CT 2

CT 3

3 x Standard

Current Transformers

Plug-in Energy Meter

Meter

Converter

S1 S2 S1 S2 S1 S2

- Connect up to three standard or split core CT’s (1A or 5A secondaries)

- Integrated protection circuitry