Table of Contents Table of Contents
Previous Page  83 / 320 Next Page
Information
Show Menu
Previous Page 83 / 320 Next Page
Page Background

1.68

Data is subject to errors and technical modifications.

Fuse Combination Switches

Technical Data

Commercial

Distribution

Thermal current lth (40ºC)

20A

32A

63A

100A

125A

160A

200A

Fuse size: BS

A1

A1

A2-A3

A4

B1-B2

B1-B2

B1-B3

Rated insulated voltage

Ui (V)

800

800

800

800

800

800

800

Impulse voltages Uimp

8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 12000 12000 -

Operational current Ie (A)

A B A B A B A B A B A B

A B

415V ac AC-22A/AC-23B

20 20 32 32 63 63 100 100 125 125 160 160

200 200

Motor power (kW) 400V ac

9

15

30

51

63

80

100

Reactive power 400V ac (kVAR)

15

45

25

45

55

60

75

Overload capacity

Short-circuit with fuses (kA Rms)

50

50

50

50

50

50

50

Fuse rating (A) BS 88

20

32

63

100

125

160

200

Making & Breaking Capacity

Breaking capacity 400V AC-23B

(A RMS)

160

256

500

800

1000

1280

1600

Making capacity 400V AC-22

(A RMS)

200

320

630

1000

1250

1600

2000

Withstand mechanical

(number of operations)

20,000

20,000

10,000

10,000

10,000

10,000

10,000

Tightening torque

2

2

6

9

9

9

20

Connection (mm

2

)

Minimum Cu cable section

2.5

2.5

10

25

35

50

70

Maximum Cu cable section

16

16

25

95

95

95

240

Fuse types

NIT20

NIT32

TIS63

TCP100

TF125

TF160

TF200

Thermal current l th (40ºC)

250A

315A

400A

630A

800A

Fuse size: BS

B1-B3

B1-B4

B1-B4

C1-C2

C1-C2-C3

Rated insulated voltage U i (V)

800

800

800

1000

1000

Operational current I e (A)

A = Frequent operation

B = Infrequent operation

A B A B A B A B A B

415V a.c. AC-22A/AC-23B

250 250 315 315 400 400 630 630 800 800

Motor power (kW) 400V a.c.

-

160 160 220 220 355 355 -

Reactive power 400V a.c. (kVAR)

-

125

150

2 x 125

-

Overload capacity

Short-circuit with fuses (kA Rms)

50

50

50

50

50

Fuse rating (A) BS 88

250

315

400

630

800

Making & Breaking Capacity

Breaking capacity 400V AC-23B

(A R.M.S)

2000

2520

3200

-

-

Making capacity 400V

AC-23B (A R.M.S)

2500

3150

4000

-

-

Withstand mechanical

(number of operations)

10,000

10,000

10,000

8000

8000

Tightening torque (Nm)

-

20

20

40

40

Connection (mm

2

)

Minimum Cu cable section

70

185

185

2 x 150

2 x 150

Maximum Cu cable section

240

240

240

2 x 300

2 x 300

Fuse types

TKF250

TKF315

TMF400

TTM630

TLM800