1.70
Data is subject to errors and technical modifications.
Switch Fuses & IP65 Enclosed Isolating Switch
Dimensions
Commercial
Distribution
Switch Fuses
Dimensions (mm)
Width
Height
Depth
Depth with Door Knockouts
IU44-16
115
187
61.5
-
2 x 25mm
IU44-18
125
312
73.5
-
None
IU44-11
125
312
73.5
-
None
IU44-16-D
125
312
74
96
None
IU44-18-D
125
312
74
96
None
IU44-11-D
125
312
74
96
None
Width
Height
Depth
IP65 Enclosed Isolating Switch
All dimensions are in mm and exclude the handle.
Add 27mm to the depth to allow for the handle on 10-25A products.
Add 32mm to the depth to allow for the handle on 40-80A products.
Description
Dimensions (mm)
Width
Height
Depth
JG00S
10A TPN
100
136
74
JG01S
16A TPN
100
136
105
JG02S
25A TPN
100
136
105
JG03S
40A TPN
136
201
105
JG04S
63A TPN
136
201
118
JG05S
80A TPN
136
201
118
Enclosed thermal current l the
16
25
40
63
80
Rated insulation voltage U i (V)
690
690
690
690
690
Rated thermal current l the (A)
25
40
63
80
100
Rated operational current
AC21 400V Ie (A)
25
40
63
80
100
AC22 400V
16
25
40
63
100
AC22 400V cos phi 0.65
16
20
32
63
100
AC23 400V
16
20
32
63
100
AC23 400V cos phi 0.35
16
15
25
40
63
Rated operational power
AC23 230V (kW)
4
5.5
7.5
11
15
AC23 400V
7.5
11
15
22
30
Rated fused short circuit current
Back-up fuse (A)
63
63
63
80
100
R.M.S value Ik (kA)
50
50
50
50
50
Peak value (kA)
5.4
6.6
7.2
8.3
8.7
Rated short circuit making capacity (Icm) (kA) 690V
2.5
2.5
2.5
3.3
3.3
Rated short time withstand current (lcw) (kA) 690V (1s)
1
1.1
1.6
1.7
2.3
Rated breaking capacity Icn (A) AC23
400V cos phi 0.35
250
270
320
480
504
Electrical endurance (number of operations)
3000
3000
3000
3000
-
Mechanical endurance (number of operations)
50,000
50,000
50,000
50,000
-
Terminals mm
2
1.5 - 16
1.5 - 16
1.5 - 16
2.5 - 35
2.3 - 35
Max. thermal torque (Nm)
1.8
1.8
1.8
2.5
2.5