1.59

Data is subject to errors and technical modifications.

Invicta 3 Panelboard

Technical Data

Commercial

Distribution

Characteristics

250A

400A

630 / 800A

800A

Series

JN2**

JF4**

JF6**/JF8**

JHF8**

Busbar current rating

250A

400A

800A

800A (for 800A MCCB only)

Busbar type

Type B Fully Shrouded Copper

Busbar rated short-time with-

stand current

25kA for 1 sec

35kA for 1 sec

35kA for 1 sec

35kA for 1 sec

Internal separation

Form 3A

Incoming

Up to 250A MCCB, MCS Up to 400A MCCB, MCS Up to 630A MCCB, 800A LBS 800A MCCB

Outgoing

16 - 125A max.

16 - 125A max.

16 - 125A

100A - 250A

16 - 125A

100A - 250A

Voltage rating in a.c.

415V

415V

415V

415V

IP Protection

IP30

Enclosure body type

Steel

Enclosure paint type

Powder coat Grey White BS 4800 00A01

Cable entry

Via Gland Plates

Terminal Connection capacity

Incoming earth terminal

M8

M10

M10

M10

Incoming neutral terminal

M8

M12

M12

M12

Outgoing earth terminals

Up to 50mm²

Up to 50mm²

Up to 50mm²

Up to 50mm²

Outgoing neutral terminals

Up to 50mm²

Up to 50mm²

16A - 125A: Up to 50mm

2

100A - 250A: M8 Stud

16A - 125A: Up to 50mm

2

100A - 250A: M8 Stud

Enclosure earth stud

M8

M10

M10

M10

Installation

Mounting