1.54
Data is subject to errors and technical modifications.
Invicta 3 Metered Incomer
Technical Data
Commercial
Distribution
Interface Characteristics
JKD125PM
JKD125TPM
JKD250PM
JKD250TPM
Rated & operational voltage
(U n / U e
)
415V a.c. 50Hz
415V a.c. 50Hz
415V a.c. 50Hz
415V a.c. 50Hz
Rated insulation voltage (U i )
690V a.c. 50Hz
690V a.c. 50Hz
690V a.c. 50Hz
690V a.c. 50Hz
Rated impulse withstand voltage
(U imp
)
4kV
4kV
4kV
4kV
Rated current of the Assembly
(I nA
)
125A
Right Side Pan Assembly
(I n
) 125A
Left Side Pan Assembly
(I n
) 125A
125A
Right Side Pan Assembly
(I n
) 125A
Middle Pan Assembly
(I n ) 125A
Left Side Pan Assembly
(I n
) 125A
250A
Right Side Pan Assembly
(I n ) 250A
Left Side Pan Assembly
(I n ) 250A
250A
Right Side Pan Assembly
(I n ) 200A
Middle Pan Assembly
(I n ) 200A
Left Side Pan Assembly
(I n ) 200A
Rated conditional short-circuit
current of the assembly (I cc )
10kA with equipment and
arrangements specified
in Hager’s technical
documentation/catalogue
10kA with equipment and
arrangements specified
in Hager’s technical
documentation/catalogue
10kA with equipment and
arrangements specified
in Hager’s technical
documentation/catalogue
10kA with equipment and
arrangements specified
in Hager’s technical
documentation / catalogue
Protection against electric shock Equipment shall be installed
in an electrical system
conforming to IEC 60364 /
BS 7671
Equipment shall be installed
in an electrical system
conforming to IEC 60364 /
BS 7671
Equipment shall be installed
in an electrical system
conforming to IEC 60364 /
BS 7671
Equipment shall be installed
in an electrical system
conforming to IEC 60364 /
BS 7671
Rated frequency (f n )
50 Hz
50 Hz
50 Hz
50 Hz
Pollution degree
2
2
2
2
Types of system earthing
for which the ASSEMBLY is
designed
TNC-S, TN-S and TT when
installed in an electrical
system conforming to BS
7671
TNC-S, TN-S and TT when
installed in an electrical
system conforming to BS
7671
TNC-S, TN-S and TT when
installed in an electrical
system conforming to BS
7671
TNC-S, TN-S and TT when
installed in an electrical
system conforming to BS
7671
Intended locations
Indoor use only
Indoor use only
Indoor use only
Indoor use only
Degree of protection
IP3XD with Door Closed
IP2XC with Door Open
IP3XD with Door Closed
IP2XC with Door Open
IP3XD with Door Closed
IP2XC with Door Open
IP3XD with Door Closed /
IP2XC with Door Open
Intended use
Distribution boards intended
to be operated by ordinary
persons (DBO)
Distribution boards intended
to be operated by ordinary
persons (DBO)
Distribution boards intended
to be operated by ordinary
persons (DBO)
Distribution boards intended
to be operated by ordinary
persons (DBO)
Electromagnetic compatibility
(EMC) classification
EMC Environment B
EMC Environment B
EMC Environment B
EMC Environment B
External design
Wall-mounted, surface type,
enclosed assembly.
Wall-mounted, surface type,
enclosed assembly.
Wall-mounted, surface type,
enclosed assembly.
Wall-mounted, surface type,
enclosed assembly.
Mechanical impact protection IK05
IK05
IK05
IK05
The type of construction
Fixed parts
Fixed parts
Fixed parts
Fixed parts
Incoming Line Terminal
M8
M8
M8
M8
Incoming Neutral Terminal
M8 Lug
M8 Lug
M8 Lug
M8 Lug
Enclosure Earth Stud
M8
M8
M8
M8