Invicta 3 Metered Incomer

Technical Data

Commercial

Distribution

Interface Characteristics

JKD125PM

JKD125TPM

JKD250PM

JKD250TPM

Rated & operational voltage

(U n / U e

)

415V a.c. 50Hz

415V a.c. 50Hz

415V a.c. 50Hz

415V a.c. 50Hz

Rated insulation voltage (U i )

690V a.c. 50Hz

690V a.c. 50Hz

690V a.c. 50Hz

690V a.c. 50Hz

Rated impulse withstand voltage

(U imp

)

4kV

4kV

4kV

4kV

Rated current of the Assembly

(I nA

)

125A

Right Side Pan Assembly

(I n

) 125A

Left Side Pan Assembly

(I n

) 125A

125A

Right Side Pan Assembly

(I n

) 125A

Middle Pan Assembly

(I n ) 125A

Left Side Pan Assembly

(I n

) 125A

250A

Right Side Pan Assembly

(I n ) 250A

Left Side Pan Assembly

(I n ) 250A

250A

Right Side Pan Assembly

(I n ) 200A

Middle Pan Assembly

(I n ) 200A

Left Side Pan Assembly

(I n ) 200A

Rated conditional short-circuit

current of the assembly (I cc )

10kA with equipment and

arrangements specified

in Hager’s technical

documentation/catalogue

10kA with equipment and

arrangements specified

in Hager’s technical

documentation/catalogue

10kA with equipment and

arrangements specified

in Hager’s technical

documentation/catalogue

10kA with equipment and

arrangements specified

in Hager’s technical

documentation / catalogue

Protection against electric shock Equipment shall be installed

in an electrical system

conforming to IEC 60364 /

BS 7671

Equipment shall be installed

in an electrical system

conforming to IEC 60364 /

BS 7671

Equipment shall be installed

in an electrical system

conforming to IEC 60364 /

BS 7671

Equipment shall be installed

in an electrical system

conforming to IEC 60364 /

BS 7671

Rated frequency (f n )

50 Hz

50 Hz

50 Hz

50 Hz

Pollution degree

2

2

2

2

Types of system earthing

for which the ASSEMBLY is

designed

TNC-S, TN-S and TT when

installed in an electrical

system conforming to BS

7671

TNC-S, TN-S and TT when

installed in an electrical

system conforming to BS

7671

TNC-S, TN-S and TT when

installed in an electrical

system conforming to BS

7671

TNC-S, TN-S and TT when

installed in an electrical

system conforming to BS

7671

Intended locations

Indoor use only

Indoor use only

Indoor use only

Indoor use only

Degree of protection

IP3XD with Door Closed

IP2XC with Door Open

IP3XD with Door Closed

IP2XC with Door Open

IP3XD with Door Closed

IP2XC with Door Open

IP3XD with Door Closed /

IP2XC with Door Open

Intended use

Distribution boards intended

to be operated by ordinary

persons (DBO)

Distribution boards intended

to be operated by ordinary

persons (DBO)

Distribution boards intended

to be operated by ordinary

persons (DBO)

Distribution boards intended

to be operated by ordinary

persons (DBO)

Electromagnetic compatibility

(EMC) classification

EMC Environment B

EMC Environment B

EMC Environment B

EMC Environment B

External design

Wall-mounted, surface type,

enclosed assembly.

Wall-mounted, surface type,

enclosed assembly.

Wall-mounted, surface type,

enclosed assembly.

Wall-mounted, surface type,

enclosed assembly.

Mechanical impact protection IK05

IK05

IK05

IK05

The type of construction

Fixed parts

Fixed parts

Fixed parts

Fixed parts

Incoming Line Terminal

M8

M8

M8

M8

Incoming Neutral Terminal

M8 Lug

M8 Lug

M8 Lug

M8 Lug

Enclosure Earth Stud

M8

M8

M8

M8