Page Background

1.55

Data is subject to errors and technical modifications.

Invicta 3 Metered Incomer

Technical Data & Dimensions

Commercial

Distribution

Meter Characteristics

Supply

60 to 300V AC, 50/60Hz (±5%)

Serial Communication

Interface Standard and Protocol

RS485 and MODBUS RTU

Input (CT)

Pluggable RJ45

Input 1/ Input 2

Output

Pulse Output:

Voltage Range : 24V DC max

Current Capacity :

100mA max

Pulse Duration :

Selectable Between 0.1 to 2.0sec

Pulse Weight :

Selectable between 0.01 to 9.99kWh

Accuracy of meter

Measurement

Accuracy

Voltage VL-N

0.5% of full range

Voltage VL-L

0.5% of full range

Current A

0.5% of full range

Frequency

For L-N Voltage >20V

For L-L Voltage >35V"

0.1% of full range

Active power

1.0% of full range

Apparent Power

1.0% of full range

Reactive Power

1.0% of full range

Power Factor

±0.01% of full Range

Active Energy

1.0% of full range

Reactive Energy

1.0% of full range

Max/Min Active Power

1.0% of full range

Max/Min Reactive Power

1.0% of full range

Max Apparent Power

1.0% of full range

Power Consumption

Less than 8VA

L1 L2 L3

N

Depth

Height

Width

L1 L2 L3

N

Depth

Width

Height

Dual & Triple Meter Incomers

Dimensions (mm)

Height

Width

Depth

JKD125PM

625

930

132.5

JKD125TPM

625

1395

132.5

JKD250PM

625

930

132.5

JKD250TPM

625

1395

132.5