1.55
Data is subject to errors and technical modifications.
Invicta 3 Metered Incomer
Technical Data & Dimensions
Commercial
Distribution
Meter Characteristics
Supply
60 to 300V AC, 50/60Hz (±5%)
Serial Communication
Interface Standard and Protocol
RS485 and MODBUS RTU
Input (CT)
Pluggable RJ45
Input 1/ Input 2
Output
Pulse Output:
Voltage Range : 24V DC max
Current Capacity :
100mA max
Pulse Duration :
Selectable Between 0.1 to 2.0sec
Pulse Weight :
Selectable between 0.01 to 9.99kWh
Accuracy of meter
Measurement
Accuracy
Voltage VL-N
0.5% of full range
Voltage VL-L
0.5% of full range
Current A
0.5% of full range
Frequency
For L-N Voltage >20V
For L-L Voltage >35V"
0.1% of full range
Active power
1.0% of full range
Apparent Power
1.0% of full range
Reactive Power
1.0% of full range
Power Factor
±0.01% of full Range
Active Energy
1.0% of full range
Reactive Energy
1.0% of full range
Max/Min Active Power
1.0% of full range
Max/Min Reactive Power
1.0% of full range
Max Apparent Power
1.0% of full range
Power Consumption
Less than 8VA
L1 L2 L3
N
Depth
Height
Width
L1 L2 L3
N
Depth
Width
Height
Dual & Triple Meter Incomers
Dimensions (mm)
Height
Width
Depth
JKD125PM
625
930
132.5
JKD125TPM
625
1395
132.5
JKD250PM
625
930
132.5
JKD250TPM
625
1395
132.5