Invicta 3 Metered Board

Technical Data

Commercial

Distribution

Interface Characteristics

Dual Power & Lighting Boards

Triple Power, Lighting & Services Board

Rated & operational voltage (U n / U e

)

415V a.c. 50Hz

415V a.c. 50Hz

Rated insulation voltage (U i

)

690V a.c. 50Hz

690V a.c. 50Hz

Rated impulse withstand voltage (U imp

)

4kV

4kV

Rated current of the Assembly (I nA

)

125A

200A

Rated current of pan assembly

Lower Pan (I n ) = 125A (RDF=1)

Upper Pan (I n ) = 125A (RDF=1)

Lower Pan (I n ) = 125A (RDF=1)

Middle Pan (I n ) = 125A (RDF=1)

Upper Pan (I n ) = 125A (RDF=1)

Rated current of an Outgoing Circuit (I nc )

MCB 0.5A - 63A (marked rated current on device)

RCBO 6A - 45A (marked rated current on device)

MCB 0.5A - 63A (marked rated current on device)

RCBO 6A - 45A (marked rated current on device)

Rated conditional short-circuit current of the

assembly (I cc

)

10kA with equipment and arrangements specified in

Hager’s technical documentation/catalogue

10kA

1

with equipment and arrangements specified

in Hager’s technical documentation/catalogue

Protection against electric shock

Equipment shall be installed in an electrical system

conforming to IEC 60364 / BS 7671

Equipment shall be installed in an electrical

system conforming to IEC 60364 / BS 7671

Rated Diversity Factor (RDF) / Values of assumed

loading

10 way to 24 way = 0.5 Note: RDF only applies to

continuously and simultaneously loaded circuits.

10 way to 24 way = 0.5 Note: RDF only applies to

continuously and simultaneously loaded circuits.

Rated frequency (f n )

50 Hz

50 Hz

Pollution degree

2

2

Types of system earthing for which the assembly is

designed

TNC-S, TN-S and TT when installed in an electrical

system conforming to BS 7671

TNC-S, TN-S and TT when installed in an electrical

system conforming to BS 7671

Intended locations

Indoor use only

Indoor use only

Stationary Assembly

Degree of protection

IP3XD with Door Closed

IP2XC with Door Open

IP3XD with Door Closed

IP2XC with Door Open

Intended use

Distribution boards intended to be operated by

ordinary persons (DBO)

Distribution boards intended to be operated by

ordinary persons (DBO)

Electromagnetic compatibility (EMC) classification EMC Environment B

EMC Environment B

External design

Wall-mounted, surface type, enclosed assembly.

Wall-mounted, surface type, enclosed assembly.

Mechanical impact protection

IK05

IK05

The type of construction

Fixed parts

Fixed parts

DBO Type

Type B DBO

Type B DBO

Incoming Line Terminal

70mm

2

(switch disconnector)

70mm

2

(switch disconnector

Incoming Neutral Terminal

50mm

2

Cage

50mm

2

Cage

Enclosure Earth Stud

M8

M8

Standards

BS EN 61439-3

BS EN 61439-3