1.51

Data is subject to errors and technical modifications.

Invicta 3 Metered Board, Dual Power & Lighting Board

Technical Data & Dimensions

Commercial

Distribution

Meter Characteristics

Supply

60 to 300V AC, 50/60Hz (±5%)

Serial Communication

Interface Standard and Protocol

RS485 and MODBUS RTU

Input (CT)

Pluggable RJ45

Input 1/ Input 2

Output

Pulse Output:

Voltage Range : 24V DC max

Current Capacity :

100mA max

Pulse Duration :

Selectable Between 0.1 to 2.0sec

Pulse Weight :

Selectable between 0.01 to 9.99kWh

Accuracy of meter

Measurement

Accuracy

Voltage VL-N

0.5% of full range

Voltage VL-L

0.5% of full range

Current A

0.5% of full range

Frequency

For L-N Voltage > 20V

For L-L Voltage > 35V"

0.1% of full range

Active power

1.0% of full range

Apparent Power

1.0% of full range

Reactive Power

1.0% of full range

Power Factor

±0.01% of full Range

Active Energy

1.0% of full range

Reactive Energy

1.0% of full range

Max/Min Active Power

1.0% of full range

Max/Min Reactive Power

1.0% of full range

Max Apparent Power

1.0% of full range

Power Consumption

Less than 8VA

Dual Power & Lighting Boards

Dimensions (mm)

Height

Width

Depth

JKD146PM

1100

465

165.5

JKD166PM

1100

465

165.5

JKD164PM

1100

465

165.5

JKD168PM

1250

465

165.5

JKD188PM

1250

465

165.5

JKD186PM

1250

465

165.5

JKD1416PM

1400

465

165.5

JKD1164PM

1400

465

165.5

JKD1812PM

1400

465

165.5

JKD1128PM

1400

465

165.5

JKD11212PM

1400

465

165.5

Triple Power, Lighting & Services Board

Dimensions (mm)

Height

Width

Depth

JKD2884PM

1850

465

165.5

L1 L2 L3

L1

L2

L3

L1

L2

L3

ISOLATESUPPLY

BEFOREREMOVINGCOVER

UN

LOCK

UN

LOCK

L1 L2 L3

L1

L2

L3

L1

L2

L3

L1

L2

L3

ISOLATESUPPLY

BEFOREREMOVINGCOVER

UN

LOCK

UN

LOCK

L1 L2 L3

L1

L2

L3

Depth

Width

Height