Cablelink Plus Single Pan

Technical

Cablelink Plus Single Pan

Cablelink Plus Single Pan Box provides an effective interface

between services beneath the floor and the office environment.

Robust design, constructed with a single piece metal frame, the

floorbox is available with 1 to 4 compartments and a choice of

95

mm or 70mm box depths.

l

Tested to EN50085-2-2 to accept 5000N load

l

Designed to support Cat 6 structured cabling systems

l

70

mm pan depth has been designed for those applications with

shallow voids

l

Device plate can be adjusted to provide increased wiring space or

greater plug top clearance

l

Self closing lid in accordance with IEC 61534-22

l

Quality, reliability and safety come as standard

l

Provision of RCD protection supports compliance with the 17th Edition

Wiring Regulations

l

5

year guarantee

Materials

All plastic components are manufactured from UL94 V2 rated nylon.

Metal components are manufactured from pre-galvanised steel, accessory

plates are powdercoated or colour coated.

Standards

The Cablelink Plus Single Pan Box supports compliance with the

latest edition of the IEE Wiring Regulations (BS 7671) and to

BS EN50085 Part 1 and EN50085 Part 2-2. Additionally the floorboxes also

comply with IEC 60670 Parts 1 and 23.

Installation

Cablelink Plus Single Pan boxes should not be installed in the following

situations:

l

Where protruding electrical cables are likely to cause a safety hazard

l

In passageways, especially where trolleys or other vehicles may be used

l

On escape routes, as this may impede the evacuation of the occupants

from the building

l

Where the cleaning methods employed result in the formation of pools

of liquid or soaking of the floor surface

l

Desks, chairs, shelving, filing cabinets should not be positioned on the

floorbox as this will interfere with opening the lid

RAL Colours

Grey (GRY) = RAL 7011

Light Grey (LGY) = RAL 7046

Load Testing

Load Testing of Floorboxes to draft pr EN50085 Part 2-2 (Clauses 10.5.103

and 10.5.104).

The floorboxes have been tested to and comply with the loading requirements

of draft pr EN50085 Part 2-2 (Cable trunking systems and cable ducting

systems for electrical installations Part 2-2: Particular requirements for

cable trunking systems and cable ducting systems intended for mounting

underfloor, flushfloor, or onfloor).

There are two loading criteria for the floorboxes - one with a point loading

to replicate foot traffic for example, and the other, with a large plate to

replicate fork trucks and heavier larger loads for example. For both loading

criteria the maximum allowable deflection under load is 6mm and the

maximum permanent deflection after the load has been removed is 3mm.

The Lid Deflection (loading) graph shows that the maximum point loading

classification achieved is 3kN and the maximum large plate loading

classification achieved is 5kN.

The Permanent Deflection graph shows the permanent deflection from

the test wheel loading at 3kN is 0.55mm and large plate loading at 5kN is

0.4

mm. This is well within the maximum allowable deflection of 3.0mm. The

loading position is the centre of the lid.

Note: This test data specifically refers to the 265x265mm sized floorbox

frame assembly. The other floorbox sizes also comply with the required

test criteria. Declarations of conformity are available on request for the

entire range.

Lid Deflection – Cablelink Plus 265x265mm

Frame Assembly

Permanent Deflection After Removal of Load

Cablelink Plus 265x265mm Frame

0

1

2

3

4

5

6

0.5

1

1.5

2

2.5

3

3.5

4

Load (kN)

Deflection under Load (mm)

Point Loading

Plate Loading

Maximum Allowable Deflection

Under Load (6mm)

7

4.5

5

0

0.5

1

1.5

2

2.5

3

3.5

Large Plate Load (5kN)

Point Load (3kN)

Permanent Deflection (mm)

Maximum Allowable

Permanent Deflection (3mm)

Cat 6 Compatibility

With the introduction of Cat 6 data cabling the orientation and depth of

many data outlets has changed resulting in the need for greater backbox

depths and wiring space to accommodate these longer data outlet. No

longer is a 35mm wiring space sufficient to ensure data terminations can

be made to the manufacturer’s recommendations to prevent transmission

losses. As a result MK has introduced 45mm wiring space for the Cablelink

Plus Floorbox systems (as well as for the Prestige 3D wall trunking system.)

This easily accommodates the longer Cat 6 data outlets and leaves sufficient

space for the data cable to run underneath it.