raised floor systems

customer services +44 (0)1745 532343

Interact Underfloor

Technical

Interact Underfloor Power

Technical Specification

Underfloor 63A and 40A – complies with BS EN 61534:2003

Manufactured within ISO 9000-9002 environment.

Electrical Specification

63

A 40A

Rated Current

63

40

A

Rated Voltage

480

480

V

Frequency

50/60 50/60

Hz

Conditional Short Circuit Rating

16

16

kA

Resistance per Copper Conductor

(

At ambient temperature 20ºC)

1.3

3.0

m

Ω

/

m

Impedance per Copper Conductor

(

At ambient temperature 20ºC)

1.3

1.3

m

Ω

/

m

Volt Drops

(

Full load, concentrated at one end) (Line + Neutral)

Powertrack

2.9

2.9

mV/A/m

Feed Unit

0.6

0.6

mV/A

Tap-off Connection

1.6

1.6

mV/A

+ 4mm

2

Cable

10

10

mV/A/m

+ 2.5mm

2

Cable

18

18

mV/A/m

Joint

0.6

0.6

mV/A

Flexible interlink Unit

0.8

0.8

mV/A

+ 10mm

2

Cable

4.0

4.0

mV/A/m

Earth Fault Loop Impedance

Line Conductor

1.5

1.5

m

Ω

/

m

Earth

Case

1.0

1.0

m

Ω

/

m

Copper

1.5

1.5

m

Ω

/

m

Copper + Case

0.75

0.75

m

Ω

/

m

Feed Unit (Line + Earth)

0.6

0.6

m

Ω

Tap-off Connection (Line + Earth)

m

Ω

+ 4mm

2

Cable R1 + R2

10

10

m

Ω

/

m

+ 2.5mm

2

Cable R1 + R2

18

18

m

Ω

/

m

Joint (Line + Earth)

0.6

0.6

m

Ω

Flexible Interlink Unit (Line + Earth)

0.8

0.8

m

Ω

+ 10mm

2

Cable R1 + R2

3.7

3.7

m

Ω

/

m

Mechanical Data

63

A 40A

Max. No. of Copper Conductors

5

5

Conductor Cross Section Area (Nominal) 14.4

14.4

mm

2

Powertrack Casing Copper Equivalent

(

Where Casing is Protective Earth)

14.5

14.5

mm

2

Cable Termination Capacity

16

16

mm

2

Tap-off Cable 32A

4.0

4.0

mm

2

Tap-off Cable 13A

2.5

2.5

mm

2

Tap-off Conduit Sizes

16/20 16/20

Ø

mm

Flexible Interlink Cable

10

10

mm

2

Flexible Interlink Conduit

25

25

Ø

mm

Integral Feed Conduit Entry

1

x 25 1 x 25

Ø

mm

Feed Conduit Entry

2

x 25 2 x 25

Ø

mm

IP Rating

4

X

4

X

Materials Specification

Powertrack Casing, Feeds and Brackets Galvanised Steel

Conductors

High Conductivity Copper

Dust cover

Powertrack Insulators

63

A – polyamide and Polyester

40

A – PVC Sockets / Tap-off

Plug / Joint

Mouldings

Noryl SE1 (Modified PPO)

Shutter

Polycetal

Tap-off/Interlink Flexible Conduit

Galvanised Steel

Tap-off Cable (Singles in Conduit)

LSF Cable to BS 7211 (PVC Cable

to BS 6004 available on request)

Tap-off Cable (Multi-core)

Multi-core Cable to BS 6500 &

BS 7211 LSF cable standard (PVC

Cable available on request)

Tap-off Pins

Line, Neutral & Copper Earth

Copper and Phosphorous

Bronze, tin plated

Casing Earth

Brass, tin plated

Flexible Interlink Cable

10

mm

2

cable to BS 6231

3

m is actually 2.7/2.8 fully stretched shortened by 0.1 - 0.2m of slack to

ensure remains flexible when wired up to module/