79
Interact Underfloor
Technical
technical hotline +44 (0)1268 563720
raised floor systems
Interact Underfloor Power
ø16/20mm CONDUIT
ASSEMBLY
77
mm
53.5
mm
22.5
mm
50.5
mm
ø25mm
KNOCKOUT
ø25mm HOLE
1.2, 2.4
OR 3.6m LENGTHS
5.4
m
5.4
m
5.4
m
2.7
m
2.7
m
3
m TAP-OFFS GIVE 100% FLOOR
COVERAGE WITH
SOCKETS POSITIONED
EVERY 300mm
2.7
m
2.7
m
ø16/20mm CONDUIT
ASSEMBLY
77
mm
53.5
mm
22.5
mm
50.5
mm
ø25mm
KNOCKOUT
ø25mm HOLE
1.2, 2.4
OR 3.6m LENGTHS
Typical floor layout
Dimensions
Elevating fixing Brackets should be positioned within 300mm from either end of a track run and either side of all joints.
Minimum support
requirement:
3.6
metre length =
4
brackets equally spaced
2.4
metre length =
3
brackets equally spaced
1.2
metre length =
2
brackets equally spaced
300
mm max
300
mm max