raised floor systems

Cablelink Plus Modular

Technical

Cablelink Plus Modular Floorbox

Cablelink Plus Raised Modular Floorboxes have been specifically

engineered to ensure robustness, a faster installation and maximum

life span flexibility.

l

Tested to EN50085-2-2 to accept 5000N load

l

Quick release blades ensure a fast and simple installation

l

Designed to support Cat 6 structured cabling systems

l

Choice of two frame sizes provide 3 and 4 module solutions to suit all

applications

l

Self Closing lid in accordance with IEC 61534-22

l

Wide range of power and data accessories available to meet all

requirements

l

Quality, reliability and safety come as standard

l

Provision of RCD protection supports compliance with the 17th Edition

Wiring Regulations

l

5

year guarantee

Materials

All plastic components are manufactured from UL94 V2 rated nylon.

Metal components are manufactured from pre-galvanised steel, accessory

plates are powdercoated or colour coated.

RAL Colours

Grey (GRY) = RAL 7011

Light Grey (LGY) = RAL 7046

Standards

The Cablelink Plus Modular Floorbox supports compliance with the

latest edition of the IEE Wiring Regulations (BS 7671:2008) and to

BS EN50085 Part 1 and EN50085 Part 2-2. Additionally the floorboxes also

comply with IEC 60670 Parts 1 and 23.

Installation

Cablelink Plus Modular boxes should not be installed in the following

situations:

l

Where protruding electrical cables are likely to cause a safety hazard

l

In passageways, especially where trolleys or other vehicles may be used

l

On escape routes, as this may impede the evacuation of the occupants

from the building

l

Where the cleaning methods employed result in the formation of pools

of liquid or soaking of the floor surface

l

Desks, chairs, shelving, filing cabinets should not be positioned on the

floorbox as this will interfere with opening the lid

Load Testing

Load Testing of Floorboxes to draft pr EN50085 Part 2-2 (Clauses 10.5.103

and 10.5.104).

The floorboxes have been tested to and comply with the loading requirements

of draft pr EN50085 Part 2-2 (Cable trunking systems and cable ducting

systems for electrical installations Part 2-2: Particular requirements for

cable trunking systems and cable ducting systems intended for mounting

underfloor, flushfloor, or onfloor).

There are two loading criteria for the floorboxes - one with a point loading

to replicate foot traffic for example, and the other, with a large plate to

replicate fork trucks and heavier larger loads for example. For both loading

criteria the maximum allowable deflection under load is 6mm and the

maximum permanent deflection after the load has been removed is 3mm.

The loading position is the centre of the lid.

The Lid Deflection (loading) graph shows that the maximum point loading

classification achieved is 3kN and the maximum large plate loading

classification achieved is 5kN.

The Permanent Deflection graph shows the permanent deflection from

the test wheel loading at 3kN is 0.55mm and large plate loading at 5kN is

0.4

mm. This is well within the maximum allowable deflection of 3.0mm.

Note: This test data specifically refers to the 265 x 265mm sized floorbox frame

assembly. The other floorbox sizes also comply with the required test criteria.

Declarations of conformity are available on request for the entire range.

Lid Deflection – Cablelink Plus 265 x 265mm

Frame Assembly

Permanent Deflection After Removal of Load

Cablelink Plus 265 x 265mm Frame

0

1

2

3

4

5

6

0.5

1

1.5

2

2.5

3

3.5

4

Load (kN)

Deflection under Load (mm)

Point Loading

Plate Loading

Maximum Allowable Deflection

Under Load (6mm)

7

4.5

5

0

0.5

1

1.5

2

2.5

3

3.5

Large Plate Load (5kN)

Point Load (3kN)

Permanent Deflection (mm)

Maximum Allowable

Permanent Deflection (3mm)