FLOOR SYSTEMS

RAISED

For a full range of corresponding products,

see pages 383-386 in the product selector.

Cablelink Plus

Single Pan Technical

Cablelink Plus Single Pan

Cat 6 and Cat 7 Compatibility

With the introduction of Cat 6 and Cat 7 data cabling the orientation and depth of

many data outlets has changed resulting in the need for greater backbox depths and

wiring space to accommodate these longer data outlet. No longer is a 35mm wiring

space sufficient to ensure data terminations can be made to the manufacturer’s

recommendations to prevent transmission losses. As a result MK has introduced 45mm

wiring space for the Cablelink Plus floorbox systems (as well as for the Prestige 3D wall

trunking system.) This easily accommodates the longer Cat 6 and Cat 7 data outlets

and leaves sufficient space for the data cable to run underneath it.

Load Testing

Load Testing of Floorboxes to BS EN 50085 Part 2-2 (Clauses 10.5.103 and 10.5.104).

The floorboxes have been tested to and comply with the loading requirements of

EN 50085 Part 2-2 (Cable trunking systems and cable ducting systems for electrical

installations Part 2-2: Particular requirements for cable trunking systems and cable

ducting systems intended for mounting underfloor, flushfloor, or onfloor).

There are two loading criteria for the floorboxes – one with a point loading to replicate

foot traffic for example, and the other, with a large plate to replicate fork trucks and

heavier larger loads for example. For both loading criteria the maximum allowable

deflection under load is 6mm and the maximum permanent deflection after the load

has been removed is 3mm.

The Lid Deflection (loading) graph shows that the maximum point loading classification

achieved is 3kN and the maximum large plate loading classification achieved is 5kN.

The Permanent Deflection graph shows the permanent deflection from the test wheel

loading at 3kN is 0.55mm and large plate loading at 5kN is 0.4mm. This is well within the

maximum allowable deflection of 3.0mm. The loading position is the centre of the lid.

Lid Deflection – Cablelink Plus 265x265mm Frame Assembly

0

1

2

3

4

5

6

0.5

1

1.5

2

2.5

3

3.5

4

Load (kN)

DeflectionunderLoad (mm)

Point Loading

Plate Loading

MaximumAllowableDeflection

Under Load (6mm)

7

4.5

5

Permanent Deflection After Removal of Load – Cablelink Plus 265x265mm Frame

0

0.5

1

1.5

2

2.5

3

3.5

LargePlate Load (5kN)

Point Load (3kN)

Permanent Deflection (mm)

MaximumAllowable

PermanentDeflection (3mm)

Standards and Approvals

The Cablelink Plus Single Pan Box supports

compliance with the latest edition of the IET

Wiring Regulations (BS 7671) and to

BS EN 50085 Part 1 and EN 50085 Part 2-2.

Additionally the floorboxes also comply with

IEC 60670 Parts 1 and 23.

TECHNICAL SPECIFICATION

MATERIALS

PLASTIC COMPONENTS

Manufactured from UL94 V2 rated nylon.

METAL COMPONENTS

Manufactured from pre-galvanised steel.

Accessory plates are powdercoated or colour coated.

RAL COLOURS

Grey (GRY) = RAL 7011

Feature benefits

l

Tested to BS EN 50085-2-2 to accept 5000N load

l

Designed to support Cat 6 and Cat 7 structured

cabling systems

l

70mm pan depth has been designed for those

applications with shallow voids

l

Self closing lid in accordance with IEC 61534-22

l

Quality, reliability and safety come as standard

l

Provision of RCD protection supports

compliance with the

17th Edition Wiring Regulations

l

5 year guarantee

Installation

Cablelink Plus Single Pan boxes should not be

installed in the following situations:

l

Where protruding electrical cables are likely

to cause a safety hazard

l

In passageways, especially where trolleys or

other vehicles may be used

l

On escape routes, as this may impede the

evacuation of the occupants from the building

l

Where the cleaning methods employed result

in the formation of pools of liquid or soaking

of the floor surface

l

Desks, chairs, shelving, filing cabinets should

not be positioned on the floorbox as this will

interfere with opening the lid