BETA Monitoring

Monitoring of Electrical Values

Product overview

13/2

Siemens ET B1 · 10/2008

13

Overview

Devices

Page Field of application

Standards

Used in

Non-resid.

buildings

Residential

buildings

Industry

5

TT3 voltage relays

13/3

Monitoring the voltage of emergency

lighting in public buildings, short-time

failures of 20 ms, for ensuring

operational parameters for devices or

system components or monitoring the

neutral conductor for breaks.

IEC 60255;

DIN VDE 0435-303;

DIN VDE 0108;

DIN VDE 0435;

DIN VDE 0633

--

5

TT6 current relays

13/11

Monitoring of emergency and signal

lighting and motors.

All current relays can be short-time

overloaded and connected either with

direct measurement or through

transformers.

IEC 60255;

DIN VDE 0435-303

--

5

TT6 priority switches

13/17

For reduction of the connection fee in

accordance with German Federal

Regulations on Tariffs when used in

systems with electric storage heaters

where the continuous-flow heaters are

switched with priority.

IEC 60669 (VDE 0632);

BTO § 6 Section 4

--

--

5

TT3 fuse monitors

13/18

Monitoring of all types of low-voltage

fuses.

Can be used in asymmetric systems

afflicted with harmonics and

regenerative feedback motors.

IEC 60255;

DIN VDE 0435

--

5

TT3 phase and phase sequence

monitors

13/20

For the visual signaling of phase failures

or phase sequences in three-phase

systems.

The phase sequence is arbitrary. The

device is also suitable for 1, 2 or

3-

phase operation.

IEC 60255;

DIN VDE 0435

--

--

5

TT3 insulation monitors for

industrial applications

13/22

We recommend the use of insulation

monitors in all systems without

grounding.

Adjustable alarm value 2 to 100 k and

electrical isolation of measuring circuit,

power supply and contact voltage.

IEC 60255;

IEC 61557

--

--

7

LQ3 insulation monitors for medical

premises

13/25

For the insulation monitoring of

IT systems or load current monitoring of

IT system transformers for inadmissible

overheating.

The response value is 50 to 500 k and

is adjustable.

EN 61557-8;

IEC 61557-8;

DIN VDE 0100-710;

IEC 60364-7-710

--

--

© Siemens AG 2008