BETA Monitoring

Monitoring of Electrical Values

5

TT3 voltage relays

13/5

Siemens ET B1 · 10/2008

*

You can order this quantity or a multiple thereof.

13

Selection and ordering data

Contacts

U

e

I

e

U

c

MW DT Order No.

Price

per PU

PG PU PS*/

P. unit

Weight

per PU

approx.

V AC A V AC

Unit(s) Unit(s) kg

Overvoltage relays

For the monitoring of 1, 2 or 3 phases against N,

switching thresholds:

0.9 ... 1.3

× U

c

, 4 %

adjustable hysteresis

2

CO

230 4

230/400 2

B

5

TT3 194

027 1

1

0.150

For monitoring of 3 phase against N,

with N-conductor monitoring,

switching thresholds:

0.9 ... 1.3

× U

c

, 4 %

adjustable hysteresis

2

CO

230 4

230/400 2

B

5

TT3 195

027 1

1

0.150

Undervoltage relays

For the monitoring of 1, 2 or 3 phases against N,

with phase failure detection,

switching thresholds:

0.7

and 0.9 × U

c

,

not adjustable

1

CO

230 4

230/400 1

}

5

TT3 400

027 1

1

0.065

For the monitoring of safety light devices of 1, 2 or

3

phases against N,

with phase failure detection,

switching thresholds:

0.85

and 0.95 × U

c

,

not adjustable

1

CO

230 4

230/400 1

}

5

TT3 401

027 1

1

0.065

For the monitoring of 1, 2 or 3 phases against N,

with phase failure detection,

switching thresholds:

0.7

and 0.9 × U

c

,

not adjustable

2

CO

230 4

230/400 2

}

5

TT3 402

027 1

1

0.110

For the monitoring of 1, 2 or 3 phases against N,

with phase failure detection,

switching thresholds:

0.9 ... 0.95

× U

c

, 5 %

adjustable hysteresis

2

CO

230 4

230/400 2

A

5

TT3 403

027 1

1

0.110

For the monitoring of 3 phases against N,

with asymmetry, reverse voltage and phase failure

detection, with N-conductor monitoring,

switching thresholds:

0.7

and 0.9 × U

c

,

not adjustable

2

CO

230 4

230/400 2

B

5

TT3 404

027 1

1

0.110

For undervoltage monitoring of safety light devices

of 3-phases against N, with asymmetry,

reverse voltage and phase failure detection,

with N-conductor monitoring,

switching thresholds:

0.85

and 0.95 × U

c

,

not adjustable

2

CO

230 4

230/400 2

B

5

TT3 405

027 1

1

0.110

For the monitoring of 3 phases against N,

with asymmetry, reverse voltage and

phase failure detection,

with N-conductor monitoring,

switching thresholds:

0.7 ... 0.95

× U

c

, 5 %

adjustable hysteresis

2

CO

230 4

230/400 2

B

5

TT3 406

027 1

1

0.110

Short-time relays

For monitoring of short-time failure detection 20 ms

of 1, 2 or 3 phases against N,

with phase failure detection and

N-conductor monitoring,

switching thresholds:

0.8 ... 0.85

× U

c

,

not adjustable

2

CO

230 4

230/400 2

B

5

TT3 407

027 1

1

0.110

© Siemens AG 2008