19/66 Circuit-breakers, fuses
Residual-current devices
2010 CA08103002Z-EN
www.eaton.comResidual-currentdevices
PKNM
FIM
AZFIMP
FI
≦ 100 A
FI
125 A and Type B
Electrical
Standards and regulations
IEC/EN 61009
IEC/EN 61009
IEC/EN 60947-2
IEC/EN 61008
IEC/EN 61008
Tripping
A
250 (8/20
m
) non-delayed surge resistant
Non-delayed, S
Rated operational voltage
U
e
V AC
230
230/400
230/400
230/400
230/400
Operating limit values
V AC
196 - 253
196 - 440
196 - 440
184 - 440
184 - 440
Rated frequency
f
Hz
50
Rated fault currents
I
d
n
mA
30, 300
30, 300
30, 300
30, 100, 300, 500
30, 100, 300, 500
Rated non-tripping current
0.5 x
I
d
n
0.5 x
I
d
n
0.5 x
I
d
n
0.5 x
I
d
n
0.5 x
I
d
n
Rated fault switching
capacity
I
d
n
A
-
-
-
I
n
= 16-40 A: 500
I
n
= 63 A: 630
I
n
= 80 A: 800
I
n
= 100A: 1000
I
n
= 125 A: 1250
for type B:
60, 80 A: 800
40 A: 500
125 A: 1250
230 V
kA
6
-
-
-
-
400 V
kA
3
-
-
-
-
Sensitivity
DC and pulsed current
Pulsed current and
AC/DC
Rated switching capacity
I
cn
kA
10
As fitted FAZ
As fitted AZ
10
10
Operational switching
capacity
I
cs
kA
-
As fitted FAZ
-
-
-
Rated ultimate breaking
capacity
I
cu
-
As fitted AZ
As fitted AZ
-
-
Rated short-circuit switching
capacity
-
-
= I
cu
-
-
Rated operational current
I
e
A
6 - 40
40, 63
80, 125
16 - 100
40 - 125
Rated impulse withstand
voltage
U
imp
kV
6 (1.2/50
m
s)
-
4 (1.2/50
m
s)
6
6
Characteristic
B, C
-
-
-
-
Maximum back-up fuse as
short-circuit protective device
A gL
100
-
-
I
n
= 16 - 63 A: 63
I
n
= 80 A: 80
I
n
= 100 A: 100
I
n
= 125 A: 125
for type B:
I
n
≦ 80: 100
I
n
= 125: 125
Selectivity class
3
-
-
-
-
Lifespan
Electrical
Operations > 4000
-
> 1500
> 4000
> 2000
Mechanical
Operations -
-
> 10000
> 20000
> 5000
Mechanical
Standard front dimension
mm
45
45
45
45
45
Device height
mm
80
90
90
80
85
Terminal protection
Busbar tag shroud to BGV A2
Mounting width
mm
35 (2 SU)
70 (2 pole),
125 (4 pole)
95 (5.5 SU)
35 (2 space unit),
70 (4 space units)
70 (4 SU)
Mounting
-
Permanently
screw-connected
to FAZ
Screwed on to AZ
(2 to 4 pole)
IEC/EN 60715
top-hat rail
IEC/EN 60715
top-hat rail
Protection type
Circuit-breaker
IP20
-
-
-
-
Enclosed
IP40
IP40
IP40
IP40
IP40
Terminals top and bottom
Twin-purpose
terminals
Lift terminals
Lift terminals
Twin-purpose
terminals
Twin-purpose
terminals
Terminal capacity
Solid
mm
2
1 x 25
1 x (1 - 25)
2.5 - 50
1.5 - 35
1.5 - 50
Flexible
mm
2
-
1 x (0.75 - 16)
-
2 x 16
2 x (1.5 - 16)
Thickness of busbar material
mm
0.8 - 2
0.8 - 2
-
0.8 - 2
0.8 - 2
Admissible ambient
temperature range
°C
-25 - +40
-25 - +40
-25 - +40
-25 - +40
-25 - +40
Climatic proofing
IEC/EN 61009
IEC/EN 61009
IEC/EN 60068-2
IEC/EN 61008
IEC/EN 61008
PKNM, FIM, AZFIMP, FI