Background Image
Table of Contents Table of Contents
Previous Page  446 / 543 Next Page
Information
Show Menu
Previous Page 446 / 543 Next Page
Page Background

18/116 IZM circuit-breakers, IN switch-disconnectors

Accessories for IZM26

2010 CA08103002Z-EN

www.eaton.com

Accessories for IZM26

Auxiliary contact, overload trip switch and cell signalling switch

IZM-AS…

IZM-OTS

IZM-CS…

Rated breaking capacity

Inductive load

250 V AC

A

10

10

10

125 V DC

A

0.5

0.5

0.5

250 V DC

A

0.25

0.25

0.25

Voltage releases

IZM-ST24DC

IZM-STS24DC

IZM-ST48DC

IZM-STS48DC

IZM-ST60DC

IZM-ST110AD

IZM-STS110AD

IZM-ST230AD

IZM-STS230AD

Rated control voltage

AC 50/60 Hz

U

s

V

110 - 127

208 - 240

DC

U

s

V

24

48

60

110 - 125

220 - 250

Power consumption

AC

VA

(pick-up 450)

(pick-up 450)

DC

W (pick-up 250)

(pick-up 250)

(pick-up 250)

(pick-up 450)

(pick-up 450)

Response time of the

circuit-breaker with U

s

ms

35

35

35

35

35

Operating range

Drop-out voltage

AC operated 50/60 Hz Drop-out x U

c

pick-up voltage

pick-up x U

c

Acc. to IEC standard Acc. to IEC standard Acc. to IEC standard Acc. to IEC standard Acc. to IEC standard

Closing releases

IZM-SR24DC

IZM-SR48DC

IZM-SR60DC

IZM-SR110AD

IZM-SR230AD

Rated control voltage

AC 50/60 Hz

U

s

V

110 - 127

208 - 240

DC

U

s

V

24

48

60

110 - 125

220 - 250

Power consumption

AC

VA

(pick-up 450)

(pick-up 450)

DC

W (pick-up 250)

(pick-up 250)

(pick-up 250)

(pick-up 450)

(pick-up 450)

Response time of the

circuit-breaker with U

s

ms

40

40

40

40

40

Operating range

Drop-out voltage

AC operated 50/60 Hz Drop-out x U

c

pick-up voltage

pick-up x U

c

Acc. to IEC standard Acc. to IEC standard Acc. to IEC standard Acc. to IEC standard Acc. to IEC standard

IZM-AS, IZM-OTS, IZM-CS, IZM-S...