18/116 IZM circuit-breakers, IN switch-disconnectors
Accessories for IZM26
2010 CA08103002Z-EN
www.eaton.comAccessories for IZM26
Auxiliary contact, overload trip switch and cell signalling switch
IZM-AS…
IZM-OTS
IZM-CS…
Rated breaking capacity
Inductive load
250 V AC
A
10
10
10
125 V DC
A
0.5
0.5
0.5
250 V DC
A
0.25
0.25
0.25
Voltage releases
IZM-ST24DC
IZM-STS24DC
IZM-ST48DC
IZM-STS48DC
IZM-ST60DC
IZM-ST110AD
IZM-STS110AD
IZM-ST230AD
IZM-STS230AD
Rated control voltage
AC 50/60 Hz
U
s
V
–
–
–
110 - 127
208 - 240
DC
U
s
V
24
48
60
110 - 125
220 - 250
Power consumption
AC
VA
–
–
–
(pick-up 450)
(pick-up 450)
DC
W (pick-up 250)
(pick-up 250)
(pick-up 250)
(pick-up 450)
(pick-up 450)
Response time of the
circuit-breaker with U
s
ms
35
35
35
35
35
Operating range
Drop-out voltage
AC operated 50/60 Hz Drop-out x U
c
–
–
–
–
–
pick-up voltage
pick-up x U
c
Acc. to IEC standard Acc. to IEC standard Acc. to IEC standard Acc. to IEC standard Acc. to IEC standard
Closing releases
IZM-SR24DC
IZM-SR48DC
IZM-SR60DC
IZM-SR110AD
IZM-SR230AD
Rated control voltage
AC 50/60 Hz
U
s
V
–
–
–
110 - 127
208 - 240
DC
U
s
V
24
48
60
110 - 125
220 - 250
Power consumption
AC
VA
–
–
–
(pick-up 450)
(pick-up 450)
DC
W (pick-up 250)
(pick-up 250)
(pick-up 250)
(pick-up 450)
(pick-up 450)
Response time of the
circuit-breaker with U
s
ms
40
40
40
40
40
Operating range
Drop-out voltage
AC operated 50/60 Hz Drop-out x U
c
–
–
–
–
–
pick-up voltage
pick-up x U
c
Acc. to IEC standard Acc. to IEC standard Acc. to IEC standard Acc. to IEC standard Acc. to IEC standard
IZM-AS, IZM-OTS, IZM-CS, IZM-S...